| 2015-12-23 14:48:56 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120647 | | | 12/23/15 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL | | | N- SEE SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | 2) SHEET M02.01, KEYNOTE #12: INDICATE HOW THE EXHAUST | | | DUCT FROM THE SECOND FLOOR IS CONNECTING WITH THE ERV. | | | 3) M02.01: SHOW THE LOCATIONS OF THE ALL REQUIRED DUCT | | | SMOKE DETECTORS AND PROVIDE NOTES TO CLARIFY CONTROLS | | | OPERATIONS AND SUPERVSION- SECTION 606 FBC-14 | | | MECHANICAL. | | | 4) M02.01: NOTE #17 APPEARS TO BE POINTING TO AN | | | EXHAUST DUCT INSTEAD OF A REMOTE KEY STATION: PLEASE | | | CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|