| Plan Review Notes For Permit 15120647 |
| Permit Number |
15120647 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-29 13:45:18 | 15120647 | | | 222 LAKEVIEW AVE. # 100 | | | COMMERCIAL RENOVATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | TRANSFORMER PRIMARY AND SECONDARY CONDUCTORS FEEDING | | | PANELBOARDS ?IG? AND ?MDPB? ARE UNDERSIZED. INCREASE | | | THEIR SIZES FOR CONTINUIOUS LOADING ,APPLY THE DERATION | | | REQUIRED FOR MORE THAN THREE IN A CONDUIT AND VERIFY | | | THE FEEDERS HAVE AN AMPACITY EQUAL TO THE AMPACITY OF | | | THE SECONDAY PANELS. NEC 215.2 (A)(1), 240.21(C)(2)(1), | | | 310.15 (B)(2)(A), 408.36 | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.16, 110.22 | | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES | | | IN THE ELECTRICAL ROOM. NEC 210.8 | | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES | | | ON THE ROOF. NEC 210.8 | | | PROVIDE GFCI PROTECTION FOR CONTER TOP RECEPTACLES NEAR | | | THE SINK. NEC 210.8 | | | PROVIDE AN ENGINEERED MOUNTING DETAIL FOR HANGING THE | | | TRANSFOMERS. FBC 1604.1 | | | PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT | | | ROOM SHOWING ALL SAFETY CLEARANCES AND HEAD ROOM. NEC | | | 110.26 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|