2016-01-29 13:45:1815120647
 222 LAKEVIEW AVE. # 100
 COMMERCIAL RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 TRANSFORMER PRIMARY AND SECONDARY CONDUCTORS FEEDING
 PANELBOARDS ?IG? AND ?MDPB? ARE UNDERSIZED. INCREASE
 THEIR SIZES FOR CONTINUIOUS LOADING ,APPLY THE DERATION
 REQUIRED FOR MORE THAN THREE IN A CONDUIT AND VERIFY
 THE FEEDERS HAVE AN AMPACITY EQUAL TO THE AMPACITY OF
 THE SECONDAY PANELS. NEC 215.2 (A)(1), 240.21(C)(2)(1),
 310.15 (B)(2)(A), 408.36
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 IN THE ELECTRICAL ROOM. NEC 210.8
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 ON THE ROOF. NEC 210.8
 PROVIDE GFCI PROTECTION FOR CONTER TOP RECEPTACLES NEAR
 THE SINK. NEC 210.8
 PROVIDE AN ENGINEERED MOUNTING DETAIL FOR HANGING THE
 TRANSFOMERS. FBC 1604.1
 PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT
 ROOM SHOWING ALL SAFETY CLEARANCES AND HEAD ROOM. NEC
 110.26
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  