2016-01-06 14:02:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120647
 ADD: 222 LAKEVIEW AVE. PH 100
 CONT: TBD
 TEL: 561-373-3902 KARI
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. JAN. 06/2016
 ACTION: DENIED
  
 1) SHEET S01.00 STRUCTURAL NOTES PROVIDE A PARTIAL WIND
 DESIGN CRITERIA, MISSING ARE;
  
 1A) MEAN ROOF HEIGHT, NEGATIVE PRESSURES ARE TAKEN AT
 THE MEAN ROOF HEIGHT 2014 FBC-B TABLE 1609.7(2).
  
 1B) THE PRESSURES PROVIDED +41.2/ -45.1 DOES NOT
 PROVIDE AT WHAT SQUARE FEET THEY REPRESENT, 10 SQ. FT.,
 20 SQ. FT. 50 SQ. FT. OR 100 SQ. FT.? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 2) SHEET S01.00 LIST THE MIAMI-DADE NOA?S 11-0915.06
 (WINDOW) & 11-1013.03 (DOOR) AS THE NEW COMPONENTS &
 CLADDING THE LIMITATION ON THE FRAME HEIGHT IS 120
 INCHES IN HEIGHT AND UNIT WIDTH D.L.O. NOT TO EXCEED 48
 INCHES. SHEET S01.01 THE OVERALL HEIGHT IS 12 FOOT 4
 INCHES. PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE
 ACHIEVED IN MEETING THE ASSOCIATED WIND PRESSURES AND
 LIMITATIONS OF THE LISTED PRODUCT APPROVAL.
  
 3) PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SUBMITTED A FLORIDA APPROVAL
 WITH PRESSURE GOOD FOR +/- 50 PSF/ NOT REVIEWED BY THE
 DESIGNER OF RECORD.
 (B) WINDOWS & MULLIONS.
  
 SUBMIT (2) COPIES OF THE PRODUCT APPROVALS FOR THE
 COMPONENTS AND CLADDING LISTED ABOVE.
  
 4) SHEET A8.01 DETAILS 5 & 7 ARE CUT SECTIONS THROUGH
 THE EXTERIOR WALL AT THE ATM AND FUTURE ATM. SHEET
 S02.00 ALSO HAS A DETAIL THROUGH THIS SECTION WALL OF
 WALL. BOTH WALL SECTIONS INDICATE THE WALL FINISH IS TO
 BE ARCHITECTURAL STONE TO MATCH EXISTING BUT NEITHER
 PROVIDES FOR THE SHEATHING OF THE WALL,
 NOR THE ANCHORING OF STONE VENEER IN ACCORDANCE WITH
 1405.7.
  
 5) THE PLANS FAIL TO SHOW HOW THE ATM WILL BE ANCHORED
 IN PLACE TO MEET THE WIND PRESSURES FOR THIS LOCATION,
 MAY REQUIRE A PRODUCT APPROVAL OR ENGINEERING FOR THE
 ANCHORING OF THE UNIT. 1609.4.4.1.1.
 6) THE ATM MACHINE WILL NEED TO SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE 707.1-8.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  