| 2016-01-06 14:02:31 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120647 |
| | ADD: 222 LAKEVIEW AVE. PH 100 |
| | CONT: TBD |
| | TEL: 561-373-3902 KARI |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 06/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S01.00 STRUCTURAL NOTES PROVIDE A PARTIAL WIND |
| | DESIGN CRITERIA, MISSING ARE; |
| | |
| | 1A) MEAN ROOF HEIGHT, NEGATIVE PRESSURES ARE TAKEN AT |
| | THE MEAN ROOF HEIGHT 2014 FBC-B TABLE 1609.7(2). |
| | |
| | 1B) THE PRESSURES PROVIDED +41.2/ -45.1 DOES NOT |
| | PROVIDE AT WHAT SQUARE FEET THEY REPRESENT, 10 SQ. FT., |
| | 20 SQ. FT. 50 SQ. FT. OR 100 SQ. FT.? 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2) SHEET S01.00 LIST THE MIAMI-DADE NOA?S 11-0915.06 |
| | (WINDOW) & 11-1013.03 (DOOR) AS THE NEW COMPONENTS & |
| | CLADDING THE LIMITATION ON THE FRAME HEIGHT IS 120 |
| | INCHES IN HEIGHT AND UNIT WIDTH D.L.O. NOT TO EXCEED 48 |
| | INCHES. SHEET S01.01 THE OVERALL HEIGHT IS 12 FOOT 4 |
| | INCHES. PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE |
| | ACHIEVED IN MEETING THE ASSOCIATED WIND PRESSURES AND |
| | LIMITATIONS OF THE LISTED PRODUCT APPROVAL. |
| | |
| | 3) PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. SUBMITTED A FLORIDA APPROVAL |
| | WITH PRESSURE GOOD FOR +/- 50 PSF/ NOT REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | (B) WINDOWS & MULLIONS. |
| | |
| | SUBMIT (2) COPIES OF THE PRODUCT APPROVALS FOR THE |
| | COMPONENTS AND CLADDING LISTED ABOVE. |
| | |
| | 4) SHEET A8.01 DETAILS 5 & 7 ARE CUT SECTIONS THROUGH |
| | THE EXTERIOR WALL AT THE ATM AND FUTURE ATM. SHEET |
| | S02.00 ALSO HAS A DETAIL THROUGH THIS SECTION WALL OF |
| | WALL. BOTH WALL SECTIONS INDICATE THE WALL FINISH IS TO |
| | BE ARCHITECTURAL STONE TO MATCH EXISTING BUT NEITHER |
| | PROVIDES FOR THE SHEATHING OF THE WALL, |
| | NOR THE ANCHORING OF STONE VENEER IN ACCORDANCE WITH |
| | 1405.7. |
| | |
| | 5) THE PLANS FAIL TO SHOW HOW THE ATM WILL BE ANCHORED |
| | IN PLACE TO MEET THE WIND PRESSURES FOR THIS LOCATION, |
| | MAY REQUIRE A PRODUCT APPROVAL OR ENGINEERING FOR THE |
| | ANCHORING OF THE UNIT. 1609.4.4.1.1. |
| | 6) THE ATM MACHINE WILL NEED TO SHOW COMPLIANCE WITH |
| | THE 2014 FBC-ACCESSIBILITY CODE 707.1-8. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |