| Plan Review Notes For Permit 15120611 |
| Permit Number |
15120611 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-28 06:29:11 | 1) SHT. A-8 - THE EQUIPMENT SCHEDULE SHOWS GAS TO | | | EQUIPMENT NUMBERS E96, E99, E106 & E117. THIS HAS BEEN | | | CORRECTED ON THE EQUIPMENT SCHEDULE IN THE PLUMBING | | | DRAWINGS AND ALSO NEEDS TO BE CORRECTED ON THIS SHEET. | | | 2) SHOW THE CAPACITY OF THE EXISTING GREASE INTERCEPTOR | | | AND SUBMIT GREASE WASTE CALCULATIONS TO ENSURE THE | | | EXISTING GREASE TRAP HAS THE CAPACITY TO PERFORM AS | | | DESIGNED.FBC SEC. 107.2.1. | | | 3) THE TWO FLOOR SINKS & FLOOR DRAIN LOCATED IN THE | | | ROOM WITH THE WATER HEATEER AND THE EXISTING MOP SINK | | | ARE NOT VENTED. COMPLY WITH 2014 FPC SEC. 910 OR 914. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|