| 2016-02-25 05:59:53 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 25120611 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 212 |
| | CONT: ADCON ADVANCED CONSTRUCTION |
| | TEL: 561-856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: THURS. FEB. 25/2016 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) 2ND REQUEST. PLEASE PROVIDE A DEMO SHEET OR PROVIDE |
| | A EXISTING LAY OUT AND WHAT IS NEW FOR COMPARISON. THE |
| | INTERIOR DEMO PERMIT (15110848) WAS DESIGNED UNDERTHE |
| | SAME ARCHITECT. PLEASE NOTE THERE ARE ELEMENTS REMOVED |
| | UNDERTHE DEMO PERMIT THAT WILL CONSTITUTE NEW WORK AND |
| | HAVE TO COMPLY WITH: 2014 EXISTING BUILDING CODE LEVEL |
| | II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | ONE AREA IN QUESTION IS THE REMOVAL OF STAIR LABELED |
| | D-8. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) COMPLIED. PLEASE PROVIDE CALCULATIONS FOR PLATFORM |
| | CONSTRUCTION INCOMPLIANCE WITH 2014 FBC-B 410.4 WHERE |
| | THE PLATFORMS ARE NOT MORE THAN 30 INCHES (762 MM) |
| | ABOVE THE MAIN FLOOR, AND NOT MORE THAN ONE-THIRD OF |
| | THE ROOM FLOOR AREA AND NOT MORE THAN 3,000 SQUARE FEET |
| | (279 M2) IN AREA. |
| | |
| | 5) 2ND REQUEST. THE AREA OF RAISED PLATFORM INTHE UPPER |
| | PORTION OF THE PLANS INDICATES A RAISED PLATFORM WITH |
| | AN OCCUPANT LOAD GREATER THAN 50AND WITH ONLY 1 |
| | ACCESSIBLE MEANS OF EGRESS(RAMP). WITH THE REMOVAL OF |
| | STAIR TO THE LEFT PORTION OF THE RAISED PLATFROM (STAIR |
| | D-8 ON DEMO PERMIT) THE 2ND ACCESSIBLE MEANS OF EGRESS |
| | CAN NOW BE BUILT WITH THE 2ND RAMP ANS |
| | REQUIREDHANDRAILS. SHEET A6 SHOWS (2) RAISED PLATFORM |
| | DINING AREAS UPPER PORTION OF THE PLANS BY THE MAIN |
| | ENTRY THE OTHER TO THE LOWER PORTION OF THE MAIN ENTRY. |
| | IN BOTH DINING AREAS THE OCCUPANT LOAD IS GREATER THAN |
| | 50 AND WILL NEED TO SHOW COMPLIANCE WITH THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). THE LOWER PORTION IS NOT |
| | BEING TOUCHED, UNDER THE EXISITNG BUILDING CODE LEVEL |
| | II ALTERATIONS THIS IS NOT ADDRESSED. PLEASE NOTE THAT |
| | BEING SAID, IT DOES NOT RELIEVE THE OWNER FROM A |
| | BARRIER FREE DESIGN UNDER THE ADA AND LIABLE TO LAW |
| | SUIT. |
| | |
| | ***2003 IBC-B 1007.1 *** WHERE MORE THAN ONE MEANS OF |
| | EGRESS IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM |
| | ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE |
| | SPACE SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF |
| | EGRESS. |
| | |
| | |
| | 6) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2014 |
| | FBC-ACCESSIBILITY CODE: |
| | 6A) 2ND REQUEST. 221.2.1.1 GENERAL SEATING. WHEELCHAIR |
| | SPACES COMPLYING WITH 802.1 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH 2014 ACC.CODE SECTION 226.1 5% OF THE |
| | OVERALL SEATING. SEATING COUNT 357 SEATS/.05= 23 |
| | ACC.SEATS. |
| | |
| | |
| | 6B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. THE PLANS SHOW 3 OF |
| | THE ACCESSIBLE SEATS AT A SERVER POINT OF SALE STATION |
| | AND NOT IN THE DINING ROOM. THE PLANS DO NOT SHOW ANY |
| | ACCESSIBLE SEATING IN THE OUTDOOR SEATING AREA.THE |
| | PRIVATE DINING ROOM OR INTHE BOOTH AREAS AS WELL AS THE |
| | HIGH TOP SEATING ADJACENT TO THE BAR. |
| | |
| | 6C) SEMI-COMPLIED. THE PLANS WILL NEED TO SHOW THE |
| | ADDITIONAL ACCESSIBLE SEATING REQUIRED. 902.2 CLEAR |
| | FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305 POSITIONED FOR A FORWARD APPROACH SHALL BE |
| | PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306 |
| | SHALL BE PROVIDED. |
| | |
| | 6D) 2ND REQUEST. NOT SHOWN 902.3 HEIGHT. THE TOPS OF |
| | DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES |
| | (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | 6E) COMPLIED. |
| | |
| | 7) COMPLIED. EXISITNG. |
| | |
| | 8) PROVISO/ DEFERRED SUBMITTAL :2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | THE MECHANICAL SHEETS SHOW A ROOF TOP UNIT, OARTU-1. IS |
| | THIS A EXISITNG UNIT OR NEW? IF NEW PLEASE PROVIDE THE |
| | ENGINEERING FOR THE NEW ROOF TOP OPENING, NEW ROOF TOP |
| | CURB AND TIE DOWN OF THE CURB AS WELL AS THE TIE DOWN |
| | OF THE ROOF TOP UNIT TO THE CURB. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |