2015-12-28 14:35:091ST REVIEW 2014 MECHANICAL
 PERMIT #15120611
 12/28/15
  
 1) SHEET M2.1: OUTDOOR AIR IS BEING SUPPLIED ONLY TO
 THE CENTRAL DINING AREA VIA OARTU-1, HOWEVER NO O/A IS
 BEING SUPPLIED TO THE KITCHEN, THE PRIVATE DINING AREA,
 THE UPPER DINING AREAS, AND THE BACK BAR AREA THROUGH
 AHU'S 1, 2, & 3. PLEASE REFER TO TABLE 403.3 FBC-14
 MECHANICAL AND REVISE THE PLANS TO SHOW COMPLIANCE.
 2) M2.1: DUCT SMOKE DETECTORS ARE REQUIRED TO BE
 INSTALLED IN THE RETURN AIR SYSTEMS OF AHU'S 1, 2, & 3-
 SEE SECTION 606.2.1.
 3) PROVIDE A CHILLED WATER PIPING LAYOUT PLAN WITH PIPE
 AND PIPE INSULATION DETAILS.
 4) PROVIDE A HVAC ROOF PLAN SHOWING THE LOCATIONS OF
 THE OARTU-1, THE AC AND REFRIGERATION CONDENSERS, AND
 THE KITCHEN HOOD EXHAUST AND SUPPLY FANS. PLEASE
 INCLUDE CLEARANCES DISTANCES AS OUTLINED IN SECTIONS
 401.4 AND 501.3.1 FBC-14 MECHANICAL.
 5) PROVIDE ENGINEERED TIE DOWN DETAILS FOR THE OARTU-1
 AND THE AC CONDENSERS.
 6) PLACE A NOTE ON THE PLANS INDICATING THE KITCHEN
 HOODS, AND WALK-IN COOLER WILL BE DONE UNDER SEPARATE
 PERMITS.
  