| Plan Review Notes For Permit 15120611 |
| Permit Number |
15120611 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-22 13:28:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. SHEET A - 1 - THE OCCUPANY LOAD CALCULATIONS FOR THE | | | STORAGE AND COOLER AREA APPEAR TO BE INCORRECT THOUGH | | | IT DOES NOT ADVERSELY AFFECT THE OVER ALL LOAD, IT MUST | | | BE CORRECTED. | | | | | | 2. SHEET A - 3 - DOOR D 1-7 APPEARS TO SWING IN BOTH | | | DIRECTIONS. PROVIDE CLEAR INDICATION THAT IT SWINGS IN | | | THE PATH OF EXIT EGRESS AND THERE IS NO LATCH. | | | | | | 3. SHEET E - 2.1 - EXIT SIGNAGE IS REQUIRED FOR EXIT | | | DOORS D1-5 AND D 1-7. CONFIRM EXIT SIGNS AT THE STORAGE | | | ROOM DOOR AND THE REAR CORRIDOR DOOR. | | | | | | 4. SHEET E 2-1 AND A - 4 - EMERGENCY LIGHTING REQUIRED | | | THROUGHOUT THE OCCUPANCY ONLY 5 ARE NOTED IN THE | | | KITCHEN AREA. PROVIDE INDICATION THAT THE EXIT SIGNS | | | PROVIDE THE REQUIRED EMERGENCY LIGHTING OR PROVIDE | | | ADDITIONAL EMERGENCY LIGHTING TO MEET THE REQUIRED | | | CANDELA PER NFPA 101 THROUGHOUT THE OCCUPANCY. |
|