| 2016-01-21 18:59:41 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS |
| | REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT |
| | SHEET A1. |
| | 2. THERE ARE MANY MISSING EXIT LIGHTS TO NAME EACH. |
| | PLEASE SEE YELLOW HIGHLIGHTS ON THE REVIEWED DRAWINGS |
| | ON SHEET E2.1 |
| | 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 4. THE MANDATORY LIGHTING CONTROLS OF FBC-EC405 ARE |
| | MISSING IN THE AREAS OF THE PROPOSED STORAGE AND |
| | PROPOSED BEER COOLER. SEE LIGHTING SHEET HIGHLIGHTED IN |
| | GREEN. |
| | 5. SHEET E3.1A REFLECTS NEW STAIRS 2R & 3R. IF THESE |
| | HAVE MORE THAN 6 RISERS, NEC AND REQUIRES ILLUMINATION |
| | AND SWITCHING. |
| | 6. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. |
| | 7. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| | 8. NEC 210.8(B) GROUND FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION OTHER THAN DWELLING UNITS. ALL KITCHEN |
| | RECEPTACLES SHALL BE GFCI PROTECTED. |
| | 9. THOUGH THE FIRE ALARM REQUIRES A SEPARATE PERMIT AND |
| | SUBMITTAL, MAKE NOTE CHANGE TO DUCT DETECTOR TO |
| | INITIATE A GENERAL ALARM. |
| | 10. ACCORDING TO NFPA 72 SECTION 10.15, SMOKE DETECTOR |
| | PROTECTION IS REQUIRED IN AREAS IDENTIFIED BY AN ASTRIX |
| | * 10 ON THE FIRE ALARM FLOOR PLANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| | NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |