Plan Review Notes
Plan Review Notes For Permit 15120611
Permit Number 15120611
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-21 18:59:41THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS
 REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT
 SHEET A1.
 2. THERE ARE MANY MISSING EXIT LIGHTS TO NAME EACH.
 PLEASE SEE YELLOW HIGHLIGHTS ON THE REVIEWED DRAWINGS
 ON SHEET E2.1
 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 4. THE MANDATORY LIGHTING CONTROLS OF FBC-EC405 ARE
 MISSING IN THE AREAS OF THE PROPOSED STORAGE AND
 PROPOSED BEER COOLER. SEE LIGHTING SHEET HIGHLIGHTED IN
 GREEN.
 5. SHEET E3.1A REFLECTS NEW STAIRS 2R & 3R. IF THESE
 HAVE MORE THAN 6 RISERS, NEC AND REQUIRES ILLUMINATION
 AND SWITCHING.
 6. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 7. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 8. NEC 210.8(B) GROUND FAULT CIRCUIT-INTERRUPTER
 PROTECTION OTHER THAN DWELLING UNITS. ALL KITCHEN
 RECEPTACLES SHALL BE GFCI PROTECTED.
 9. THOUGH THE FIRE ALARM REQUIRES A SEPARATE PERMIT AND
 SUBMITTAL, MAKE NOTE CHANGE TO DUCT DETECTOR TO
 INITIATE A GENERAL ALARM.
 10. ACCORDING TO NFPA 72 SECTION 10.15, SMOKE DETECTOR
 PROTECTION IS REQUIRED IN AREAS IDENTIFIED BY AN ASTRIX
 * 10 ON THE FIRE ALARM FLOOR PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  