Plan Review Notes
Plan Review Notes For Permit 15120611
Permit Number 15120611
Review Stop B
Sequence Number 1
Notes
Date Text
2016-01-07 08:18:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 25120611
 ADD: 700 S. ROSEMARY AVE. SUITE # 212
 CONT: ADCON ADVANCED CONSTRUCTION
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: THURS. JAN. 07/2016
 ACTION: DENIED
  
 1) COVERSHEET DOES NOT SHOW A INDEX OF PLANS NOR WITHIN
 THE SET OF PLANS IS THERE A EGRESS SHEET SHOWING THE
 EGRESS THROUGH OUT THE TENANT SPACE, EXIT DIRECTIONALS,
 EXIT LIGHTS NOR EMERGENCY LIGHTS OR EMERGENCY BATTERY
 BACK UP LIGHTS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5.1.1. MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS.
 (7.) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY
  
 2) THE COVERSHEET LIST THIS AS A BUILDING TYPE II
 BUILDING. THIS BUILDING WAS BUILT UNDER THE 1997 SBCCI
 CODE AS A TYPE II BUILDING. UNDER THE 2014 FBC-B THIS
 EQUATES TO A TYPE IB BUILDING TYPE, PLEASE UPDATE
 PLANS.
  
 3) PLEASE PROVIDE A DEMO SHEET OR PROVIDE A EXISTING
 LAY OUT AND WHAT IS NEW FOR COMPARISON. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) PLEASE PROVIDE CALCULATIONS FOR PLATFORM
 CONSTRUCTION INCOMPLIANCE WITH 2014 FBC-B 410.4 WHERE
 THE PLATFORMS ARE NOT MORE THAN 30 INCHES (762 MM)
 ABOVE THE MAIN FLOOR, AND NOT MORE THAN ONE-THIRD OF
 THE ROOM FLOOR AREA AND NOT MORE THAN 3,000 SQUARE FEET
 (279 M2) IN AREA.
  
 5) SHEET A6 SHOWS (2) RAISED PLATFORM DINING AREAS ONE
 LEFT OF THE MAIN ENTRY THE OTHER TO THE RIGHT OF THE
 MAIN ENTRY. IN BOTH DINING AREAS THE OCCUPANT LOAD IS
 GREATER THAN 50 AND WILL NEED TO SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 6) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE:
 6A) 221.2.1.1 GENERAL SEATING. WHEELCHAIR SPACES
 COMPLYING WITH 802.1 SHALL BE PROVIDED IN ACCORDANCE
 WITH TABLE 221.2.1.1.
  
 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6C) 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6D) 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6E) SHEET A-17 DETAILS D & H BOTH SHOW ACCESSIBLE
 HANDRAILS FOR STAIRS BUT NO FOR RAMPS, RAMP HANDRAILS
 REQUIRE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 505.10.1 RAMPS TOP AND BOTTOM EXTENTIONS AT RAMPS.
  
 7A) SHEET A-17 SHOWS WHAT IS CALLED A EQUIPMENT
 PLATFORM, PLEASE SGOW COMPLIANCE WITH 505.3.1 AREA
 LIMITATION. THE AGGREGATE AREA OF ALL EQUIPMENT
 PLATFORMS WITHIN A ROOM SHALL BE NOT GREATER THAN
 TWO-THIRDS OF THE AREA OF THE ROOM IN WHICH THEY ARE
 LOCATED. THIS APPEARS TO BE A STORY.
  
 7B) SHOW COMPLIANCE WITH 505.3.2 AUTOMATIC SPRINKLER
 SYSTEM. WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM,
 EQUIPMENT PLATFORMS SHALL BE FULLY PROTECTED BY
 SPRINKLERS ABOVE AND BELOW THE PLATFORM, WHERE REQUIRED
 BY THE STANDARDS REFERENCED IN SECTION 903.3.
  
 8) THE MECHANICAL SHEETS SHOW A ROOF TOP UNIT, OARTU-1.
 IS THIS A EXISITNG UNIT OR NEW? IF NEW PLEASE PROVIDE
 THE ENGINEERING FOR THE NEW ROOF TOP OPENING, NEW ROOF
 TOP CURB AND TIE DOWN OF THE CURB AS WELL AS THE TIE
 DOWN OF THE ROOF TOP UNIT TO THE CURB. 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  