| 2016-01-07 08:18:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 25120611 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 212 |
| | CONT: ADCON ADVANCED CONSTRUCTION |
| | TEL: 561-856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 07/2016 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET DOES NOT SHOW A INDEX OF PLANS NOR WITHIN |
| | THE SET OF PLANS IS THERE A EGRESS SHEET SHOWING THE |
| | EGRESS THROUGH OUT THE TENANT SPACE, EXIT DIRECTIONALS, |
| | EXIT LIGHTS NOR EMERGENCY LIGHTS OR EMERGENCY BATTERY |
| | BACK UP LIGHTS. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5.1.1. MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. |
| | (7.) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY |
| | |
| | 2) THE COVERSHEET LIST THIS AS A BUILDING TYPE II |
| | BUILDING. THIS BUILDING WAS BUILT UNDER THE 1997 SBCCI |
| | CODE AS A TYPE II BUILDING. UNDER THE 2014 FBC-B THIS |
| | EQUATES TO A TYPE IB BUILDING TYPE, PLEASE UPDATE |
| | PLANS. |
| | |
| | 3) PLEASE PROVIDE A DEMO SHEET OR PROVIDE A EXISTING |
| | LAY OUT AND WHAT IS NEW FOR COMPARISON. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) PLEASE PROVIDE CALCULATIONS FOR PLATFORM |
| | CONSTRUCTION INCOMPLIANCE WITH 2014 FBC-B 410.4 WHERE |
| | THE PLATFORMS ARE NOT MORE THAN 30 INCHES (762 MM) |
| | ABOVE THE MAIN FLOOR, AND NOT MORE THAN ONE-THIRD OF |
| | THE ROOM FLOOR AREA AND NOT MORE THAN 3,000 SQUARE FEET |
| | (279 M2) IN AREA. |
| | |
| | 5) SHEET A6 SHOWS (2) RAISED PLATFORM DINING AREAS ONE |
| | LEFT OF THE MAIN ENTRY THE OTHER TO THE RIGHT OF THE |
| | MAIN ENTRY. IN BOTH DINING AREAS THE OCCUPANT LOAD IS |
| | GREATER THAN 50 AND WILL NEED TO SHOW COMPLIANCE WITH |
| | THE 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 6) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY |
| | CODE: |
| | 6A) 221.2.1.1 GENERAL SEATING. WHEELCHAIR SPACES |
| | COMPLYING WITH 802.1 SHALL BE PROVIDED IN ACCORDANCE |
| | WITH TABLE 221.2.1.1. |
| | |
| | 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 6C) 902.2 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6D) 902.3 HEIGHT. |
| | THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE |
| | 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6E) SHEET A-17 DETAILS D & H BOTH SHOW ACCESSIBLE |
| | HANDRAILS FOR STAIRS BUT NO FOR RAMPS, RAMP HANDRAILS |
| | REQUIRE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE |
| | 505.10.1 RAMPS TOP AND BOTTOM EXTENTIONS AT RAMPS. |
| | |
| | 7A) SHEET A-17 SHOWS WHAT IS CALLED A EQUIPMENT |
| | PLATFORM, PLEASE SGOW COMPLIANCE WITH 505.3.1 AREA |
| | LIMITATION. THE AGGREGATE AREA OF ALL EQUIPMENT |
| | PLATFORMS WITHIN A ROOM SHALL BE NOT GREATER THAN |
| | TWO-THIRDS OF THE AREA OF THE ROOM IN WHICH THEY ARE |
| | LOCATED. THIS APPEARS TO BE A STORY. |
| | |
| | 7B) SHOW COMPLIANCE WITH 505.3.2 AUTOMATIC SPRINKLER |
| | SYSTEM. WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO |
| | BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM, |
| | EQUIPMENT PLATFORMS SHALL BE FULLY PROTECTED BY |
| | SPRINKLERS ABOVE AND BELOW THE PLATFORM, WHERE REQUIRED |
| | BY THE STANDARDS REFERENCED IN SECTION 903.3. |
| | |
| | 8) THE MECHANICAL SHEETS SHOW A ROOF TOP UNIT, OARTU-1. |
| | IS THIS A EXISITNG UNIT OR NEW? IF NEW PLEASE PROVIDE |
| | THE ENGINEERING FOR THE NEW ROOF TOP OPENING, NEW ROOF |
| | TOP CURB AND TIE DOWN OF THE CURB AS WELL AS THE TIE |
| | DOWN OF THE ROOF TOP UNIT TO THE CURB. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |