| Plan Review Notes For Permit 15120604 |
| Permit Number |
15120604 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-03 17:08:59 | 2ND ELECTRICAL REVIEW NOTES: | | | REVIEWED FOR COMPLIANCE WITH: | | | FBC 5TH EDITION 2014 | | | NFPA 70 2011 (NEC) | | | NFPA 72 2010 | | | | | | CORRECTIONS REQUIRED: | | | 1. AS EXPRESSED IN MY PREVIOUS COMMENT #4, THE RISER | | | DIAGRAM AND THE DEVICE COUNT ON THE FLOOR PLAN DO NOT | | | MATCH. CORRECT PLANS ACCORDINGLY. | | | 2. MY COMMENT #6 HAS TO DO WITH THE SAME ISSUE AS | | | PREVIOUSLY INDICATED. THE LOAD CALCS ON THE PLANS DO | | | MATCH THE RISER DIAGRAM, BUT NOT THE FLOOR PLAN. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|