| 2015-12-30 09:40:11 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE SCOPE OF WORK AS DEFINED ON THE PLANS DOES NOT |
| | MATCH THAT INDICATED ON THE REVISION FORM. ALL |
| | DOCUMENTS HAVE TO MATCH, CORRECT AS REQUIRED. |
| | 2. THERE ARE A COUPLE OF NEW SYMBOLS APPEARING ON THE |
| | PLAN NOT INCLUDED IN THE LEGEND. CORRECT AS REQUIRED. |
| | 3. THE REQUIRED MANUFACTURERS SPEC SHEETS FOR THE NEW |
| | DEVICES SHALL ACCOMPANY THE SUBMITTAL. |
| | 4. THE RISER DIAGRAM AS PRESENTED DOES NOT MATCH THE |
| | DEVICE COUNT ON THE PLANS. WHICH IS CORRECT? REVISE |
| | PLANS ACCORDINGLY. |
| | 5. DEVICE PLACEMENT ON NEW PLANS DIFFERS IN MORE WAYS |
| | THAN INDICATED ON THE SUBMITTED REVISION FORM. CORRECT |
| | THE PLANS FOR AN ACTUAL ?AS BUILT? DRAWING. |
| | 6. THE DIFFERENCE IN THE DEVICE COUNTS WILL ALSO HAVE |
| | TO BE REFLECTED ON THE CALCS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |