2015-12-30 09:40:11THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE SCOPE OF WORK AS DEFINED ON THE PLANS DOES NOT
 MATCH THAT INDICATED ON THE REVISION FORM. ALL
 DOCUMENTS HAVE TO MATCH, CORRECT AS REQUIRED.
 2. THERE ARE A COUPLE OF NEW SYMBOLS APPEARING ON THE
 PLAN NOT INCLUDED IN THE LEGEND. CORRECT AS REQUIRED.
 3. THE REQUIRED MANUFACTURERS SPEC SHEETS FOR THE NEW
 DEVICES SHALL ACCOMPANY THE SUBMITTAL.
 4. THE RISER DIAGRAM AS PRESENTED DOES NOT MATCH THE
 DEVICE COUNT ON THE PLANS. WHICH IS CORRECT? REVISE
 PLANS ACCORDINGLY.
 5. DEVICE PLACEMENT ON NEW PLANS DIFFERS IN MORE WAYS
 THAN INDICATED ON THE SUBMITTED REVISION FORM. CORRECT
 THE PLANS FOR AN ACTUAL ?AS BUILT? DRAWING.
 6. THE DIFFERENCE IN THE DEVICE COUNTS WILL ALSO HAVE
 TO BE REFLECTED ON THE CALCS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER