Plan Review Notes
Plan Review Notes For Permit 15120589
Permit Number 15120589
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-22 03:33:451) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 PER THE WPB AMEND. TO FBC SEC. 107.3.5.3.
 2) SHOW THE SHOWER DIMENSIONS (LXW) ON THE PLAN.COMPLY
 WITH 2014 FBCR SECS. P2708, P2709.
 3) SHOW THE FIXTURE CLEARANCES/SPACING OF ALL FIXTURES
 PER 2014 FBCR SECS. P2705.1, R307.1.
 4) SHOW BOTH BUILDING DRAIN CONNECTIONS TO THE BUILDING
 SEWER ON THE PLAN AND SHOW THE SIZE OF THE SEWER. SHOW
 THE REQUIRED CLEANOUTS. 2014 FBCR SECS. P3005.2,
 P3005.2.7.
 5) SHOW THE LOCATION OF EACH WATER SERVICE & WATER
 METER ON THE PLAN AND THE LOCATION OF THE MAIN SHUTOFF
 VALVE FOR EACH STRUCTURE. 2014 FBCR SEC. P2903.9.1.
 6) HOT WATER SHALL BE SUPPLIED TO BOTH UNITS.SHOW
 LOCATION OF WATER HEATERS ON THE PLAN. 2014 FBCR SEC.
 P2801.1.
 7) SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF
 BOTH STRUCTURES ON THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) THE BACKING BOARD FOR THE WALLS IN THE SHOWERS SHALL
 COMPLY WITH 2014 FBCR SECS. R702.3.8.1, R702.4.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  