2016-01-19 19:08:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ELECTRICAL FLOOR PLANS SHOWING
 THE LOCATIONS OF ALL LIGHTING, APPLIANCE (WATER HEATER,
 ETC.) AND RECEPTACLE OUTLETS. FBC 107.2.1
  
 2) FBC- 107.3.5.3 PROVIDE AN ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 PROVIDE COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND
 SHOW CIRCUITS ON FLOOR PLAN.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  