| Plan Review Notes For Permit 15120557 |
| Permit Number |
15120557 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-21 14:05:19 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: FBC-RESIDENTIAL 5TH EDITION (2014). | | | | | | 1- ENGINEERING RAS 117 CALCULATIONS: PROVIDE 2 COPIES | | | WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED | | | BY CHAPTER 471 F.S. | | | | | | 2- PROVIDE 2 COPIES OF THE NOA 14-0529.02 REFERENCED BY | | | THE ENGINEER ON THE RAS 117 CALCULATIONS. | | | | | | 3- CONCRETE TILE NOA 14-1120.08 SUBMITTED: CLEARLY | | | IDENTIFY HOW IS THE TILE GOING TO BE FASTENED. | | | (A) IF IT'S NAILS OR SCREWS, THEN SPECIFY NAIL OR SCREW | | | TYPE AND NUMBER REQUIRED. PROVIDE CALCULATIONS SHOWING | | | THE CALCULATED MOMENT OF RESISTANCE (SEE PAGE 4 OF 6 OF | | | NOA SUBMITTED) TO VERIFY THAT TYPE AND NUMBER OF | | | NAILS/SCREWS WILL WORK. | | | | | | (B) IF USING ADHESIVE, THEN PROVIDE PRODUCT APPROVAL (2 | | | COPIES) AS REQUIRED BY FAC 61G20-3.002(33). NOTE: SEE | | | NOA SUBMITTED FOR LISTED ADHESIVES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|