| Plan Review Notes For Permit 15120556 |
| Permit Number |
15120556 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-17 17:19:58 | THIS AFTERNOON ED DELIVERED THE CORRECTED SHEET E2 AND | | | PASSED ELECTRICAL REVIEW. | | 2016-02-16 10:08:06 | REC'D A PDF FROM ED FOR REVIEW AND ADVISE.ED, I WAS | | | LOOKING THROUGH THE SUBMITTED SHEETS AND FIND THAT ALL | | | BUT COMMENT 4 HAVE BEEN SATISFACTORILY ADDRESSED. | | | THOUGH THE CODE DOES NOT DICTATE THE DISTANCE FROM THE | | | DOOR TO THE OUTLET, IT DOES SAY IN AN ACCESSIBLE | | | LOCATION. THEN IT GOES ON TO SAY THAT THE OUTLET HAS TO | | | BE A 20 AMP THAT SERVES NO OTHER LOAD. THIS MEANS A | | | THAT THIS OUTLET IS SPECIFIC TO THE SIGN AND IT SHALL | | | APPEAR ON THE PANEL SCHEDULE AS SUCH. CORRECT THAT AND | | | ALL ELSE IS FINE. |
|