Plan Review Notes
Plan Review Notes For Permit 15120556
Permit Number 15120556
Review Stop E
Sequence Number 2
Notes
Date Text
2016-03-17 17:19:58THIS AFTERNOON ED DELIVERED THE CORRECTED SHEET E2 AND
 PASSED ELECTRICAL REVIEW.
2016-02-16 10:08:06REC'D A PDF FROM ED FOR REVIEW AND ADVISE.ED, I WAS
 LOOKING THROUGH THE SUBMITTED SHEETS AND FIND THAT ALL
 BUT COMMENT 4 HAVE BEEN SATISFACTORILY ADDRESSED.
 THOUGH THE CODE DOES NOT DICTATE THE DISTANCE FROM THE
 DOOR TO THE OUTLET, IT DOES SAY IN AN ACCESSIBLE
 LOCATION. THEN IT GOES ON TO SAY THAT THE OUTLET HAS TO
 BE A 20 AMP THAT SERVES NO OTHER LOAD. THIS MEANS A
 THAT THIS OUTLET IS SPECIFIC TO THE SIGN AND IT SHALL
 APPEAR ON THE PANEL SCHEDULE AS SUCH. CORRECT THAT AND
 ALL ELSE IS FINE.