| 2016-01-28 19:39:19 | 1ST ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 5TH EDITION 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. PLEASE CLARIFY WHAT |
| | IS IF ANY YOUR SHOW WINDOW AREA. |
| | 2. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| | 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| | PADDLE FANS HEAVIER THAN 70 LBS. |
| | 4. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. YOU HAVE WHAT |
| | APPEAR TO BE THREE DOORS WHERE THIS WILL APPLY. |
| | 5. FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED. FROM |
| | THE PROVIDED PLAN AND FIXTURE SCHEDULE IT DOES NOT |
| | APPEAR THAT THERE ARE ANY EMERGENCY LIGHTS IN THE AREA |
| | IN QUESTION. |
| | 6. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT. |
| | 7. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 8. FBC-B 1011. EXIT SIGNAGE REQUIRED AT EACH OF THE |
| | EXITS AS WELL AS INDICATED BELOW. |
| | 9. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. |
| | THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, |
| | SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE |
| | SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. |
| | 10. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | 11. FBC-EC405.2 REQUIRES MANDATORY LIGHTING CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 & |
| | C405.2.4 |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |