Plan Review Notes
Plan Review Notes For Permit 15120556
Permit Number 15120556
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-29 16:01:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120556
 ADD: 777 S. FLAGLER DR. SUITE # 100R
 CONT: GOLDCON, INC.
 TEL: (305)354-2126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. DEC. 29/2015
 ACTION: DENIED
  
 1) THE COVERSHEET, SHEET T1 LIST THE CONSTRUCTION TYPE
 AS A BUILDING TYPE III-B CONSTRUCTION. NOTE THIS IS A
 HIGHRISE AND CONSTRUCTION TYPE 1A, PLEASE CORRECT.
 2014 FBC-B TABLE 503.
  
 2) SHEET A-1 INDICATES THE REMOVAL OF WHAT APPEARS ONE
 OF THE TWO REQUIRED, EGRESS DOORS. PLEASE PROVIDE A
 LIFE SAFETY PLAN FOR THE MAIN DINING ROOM, LOUNGE,
 BOARDROOM A AND BOARDROOM B. PLEASE SHOW COMPLIANCE
 WITH:
  
 2A) PLEASE SHOW THE EXITS FROM THE MAIN DINING ROOM IN
 COMPLIANCE WITH 2014 FBC-B SECTION 1015.1 & TABLE
 1015.1.
  
 2B) THE 2 EXIT ACCESS DOORS MUST MEET THE 1/3 RD
 DIAGONAL DISTANCE SERVED FOR THAT ROOM 2014 FBC-B
 1015.2.1 EXCEPTION 2.
  
 2C) EGRESS CAN NOT BE THROUGH THE SERVICE STATION
 ADJACENT TO THE BAR, SEE 2014 FBC-B 1014.2 .4 EGRESS
 SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS
 OR SPACES USED FOR SIMILAR PURPOSES.
  
 2D) THE COMBINED LOAD OF BOARD ROOMS A & B IS 72
 OCCUPANTS, PLEASE SHOW 50% OF THIS OCCUPANT LOAD GOING
 THROUGH THE DINING ROOM.
  
 2E) SHOW COMPLIANCE WITH 2014 FBC-B 1028.10.1.2 IN THE
 MAIN DINING ROOM. SEATING AT TABLE AISLE ACCESSWAY
 LENGTH. THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY
 SHALL NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE
 POINT WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS
 OF EGRESS TRAVEL TO SEPARATE EXITS.
  
 3) THE MEANS OF EGRESS ILLUMINATED EXIT SIGNAGE 2014
 FBC-B 1006.
  
 4) CAIN MILLWORK PLANS INDICATE A PORTION OF THE BAR TO
 BE ADA ACCESSIBLE. THE FLOOR PLAN SHEET A-1 DOES NOT
 SHOW WHERE THIS PORTION OF BAR IS LOCATED?
 2014 FL. ACCESSIBILITY CODE 226.1 GENERAL. WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. IN ADDITION, WHERE WORK SURFACES ARE PROVIDED
 FOR USE BY OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT
 SHALL COMPLY WITH 902.
  
 902.4.2 HEIGHT. THE TOPS OF TABLES AND COUNTERS SHALL
 BE 26 INCHES (660 MM) MINIMUM AND 30 INCHES (760 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) PLEASE NOTE IF THE EXTERIOR DOOR BEING REMOVED AND
 STILL MEETS ALL OF THE CODE REQUIREMENTS OUTLINED IN
 COMMENT # 2 A-E THEN COMPLIANCE WITH THE WIND DESIGN
 CRITERIA WILL NEED TO BE MET. PLEASE PROVIDE THE WIND
 DESIGN CRITERIA FOR THE PRESSURES PROVIDED. NEGATIVE
 PRESSURES ARE TAKEN FROM THE ROOF, POSITIVE BUILD FROM
 GRADE. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 7) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  