| Plan Review Notes For Permit 15120538 |
| Permit Number |
15120538 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-19 17:56:01 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED: | | | A) ACCORDING TO SECTION 8.1 OF RAS 117 "THE MINIMUM | | | FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN. O.C." | | | . ENGINEER SUBMITTED SOME RAS 117 CALCULATIONS WITH | | | FASTENER SPACING LESS THAN 4 IN. O.C. REVISE AS | | | REQUIRED TO COMPLY WITH SEC. 8.1. | | | | | | | | | NOTE: | | | ANY A/C UNITS REMOVAL, PROPOSED 8 NEW SKYLIGHTS, | | | RETROFIT AND NEW ROOF DRAINS, ELECTRICAL WORK, ETC. | | | REQUIRE COMPLETE INFORMATION UNDER SEPARATE PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|