2016-01-19 17:56:01RE-ROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) ACCORDING TO SECTION 8.1 OF RAS 117 "THE MINIMUM
 FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN. O.C."
 . ENGINEER SUBMITTED SOME RAS 117 CALCULATIONS WITH
 FASTENER SPACING LESS THAN 4 IN. O.C. REVISE AS
 REQUIRED TO COMPLY WITH SEC. 8.1.
  
  
 NOTE:
 ANY A/C UNITS REMOVAL, PROPOSED 8 NEW SKYLIGHTS,
 RETROFIT AND NEW ROOF DRAINS, ELECTRICAL WORK, ETC.
 REQUIRE COMPLETE INFORMATION UNDER SEPARATE PERMITS.
  