Plan Review Notes
Plan Review Notes For Permit 15120538
Permit Number 15120538
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-16 17:13:32RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- ROOF ASSEMBLIES WITH MECHANICAL ATTACHMENT NEED
 FASTENER PULL OUT TEST (TAS 105) AS REQUIRED BY
 LIGHTWEIGHT CONCRETE DECK SYSTEM LIMITATION #1 AND BY
 GENERAL LIMITATION #6 ON LAST PAGE OF NOA 15-1008.02
 SUBMITTED. PROVIDE 2 COMPLETE TAS 105 PULL OUT TEST
 REPORTS. NOTE: ENGINEER TO REVISE RAS 117 CALCULATIONS
 ACCORDINGLY.
  
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) THE BUILDING RISK CATEGORY IS INCORRECT. THIS
 BUILDING IS I-3, THEREFORE THE RISK CATEGORY IS III NOT
 II. REVISE AS AS REQUIRED. SEE TABLE 1604.5 OF FBC-5TH
 EDITION (2014). ALSO, REVISE DESIGN WIND SPEED AND ALL
 DESIGN PRESSURES AS REQUIRED BY FIGURE 1609B OF FBC-5TH
 EDITION (2014).
  
 B) CLARIFY WHY THE ENCLOSURE CLASS IS OPEN. SEC. 1609
 OF FBC-5TH EDITION (2014).
  
 NOTE:
 ANY A/C UNITS REMOVAL, PROPOSED 8 NEW SKYLIGHTS,
 RETROFIT AND NEW ROOF DRAINS, ELECTRICAL WORK, ETC.
 REQUIRE COMPLETE INFORMATION UNDER SEPARATE PERMITS.
  