| Plan Review Notes For Permit 15120538 |
| Permit Number |
15120538 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-16 17:13:32 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- ROOF ASSEMBLIES WITH MECHANICAL ATTACHMENT NEED | | | FASTENER PULL OUT TEST (TAS 105) AS REQUIRED BY | | | LIGHTWEIGHT CONCRETE DECK SYSTEM LIMITATION #1 AND BY | | | GENERAL LIMITATION #6 ON LAST PAGE OF NOA 15-1008.02 | | | SUBMITTED. PROVIDE 2 COMPLETE TAS 105 PULL OUT TEST | | | REPORTS. NOTE: ENGINEER TO REVISE RAS 117 CALCULATIONS | | | ACCORDINGLY. | | | | | | 2- ENGINEER TO REVISE RAS 117 CALCULATIONS SUBMITTED: | | | A) THE BUILDING RISK CATEGORY IS INCORRECT. THIS | | | BUILDING IS I-3, THEREFORE THE RISK CATEGORY IS III NOT | | | II. REVISE AS AS REQUIRED. SEE TABLE 1604.5 OF FBC-5TH | | | EDITION (2014). ALSO, REVISE DESIGN WIND SPEED AND ALL | | | DESIGN PRESSURES AS REQUIRED BY FIGURE 1609B OF FBC-5TH | | | EDITION (2014). | | | | | | B) CLARIFY WHY THE ENCLOSURE CLASS IS OPEN. SEC. 1609 | | | OF FBC-5TH EDITION (2014). | | | | | | NOTE: | | | ANY A/C UNITS REMOVAL, PROPOSED 8 NEW SKYLIGHTS, | | | RETROFIT AND NEW ROOF DRAINS, ELECTRICAL WORK, ETC. | | | REQUIRE COMPLETE INFORMATION UNDER SEPARATE PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|