| 2016-06-07 11:09:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120536 |
| | ADD: 2745 OKEECHOBEE BLVD. |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-568-8931 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: TUES. JUNE 07/ 2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) PROVISO: SHEET 035-A.1.1.1A & 038-A1.1.1.1D BOTH |
| | SHOW THE USE OF PLATFORM LIFTS. A REVISION IS REQUIRED, |
| | DELETING THE PLATFORM LIFT IN COMPLIANCE WITH THE 2014 |
| | FBC-ACCESSIBILITY CODE 206.7 NOT ALLOWED IN NEW |
| | CONSTRUCTION. |
| | |
| | 2) PROVISO: 090-A4-4 DETAILS 1 & 2 FLOOR STRUCTURAL |
| | MEMBERS ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD |
| | PROVIDE AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST, |
| | DEPENDING ON THE LAYOUT OF THE RAINWATER HORIZONTAL |
| | RUNS AND FIRE SPRINKLER LAYOUT WHICH HAS NOT YET BEEN |
| | PROVIDED.2014 FBC-B 406.4.1. |
| | |
| | 3) PROVISO: 2014 FBC-B SECTION [F] 406.6.3 AUTOMATIC |
| | SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE |
| | EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.2.10. |
| | |
| | 4) PROVISO: DEFERRED SUBMITTAL . DOOR TYPE (N) SHOW |
| | THEY ARE A HORIZONTAL BI-PARTING DOOR. SHEET 113-A8-0 |
| | INDICATES A DOOR TYPE (N) BUT DOES NOT INDICATE TO |
| | WHICH CODE SECTION THE DOORS ARE COMPLY 1008.1.4.2 |
| | POWER OPERATED DOORS OR 1008.1.4.3 HORIZONTAL SLIDING |
| | DOORS OR HOW MUCH FORCE IS TO BE APPLIED TO SET THE |
| | DOOR IN MOTION. DOORS SHALL BE OPENABLE BY A SIMPLE |
| | METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR |
| | EFFORT, HOW WILL THIS BE ACCOMPLISHED. |
| | |
| | 5) PROVISO/ DEFERRRED SUBMITTAL. SHEET 100-A6-2 |
| | SKYLIGHT GLAZING IS GOING TO COMPLY WITH THE 2014 FBC-B |
| | 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS. |
| | 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES. |
| | |
| | 6) PROVISO: DEFERRED SUBMITTALS. PLEASE SUBMIT PRODUCT |
| | APPROVALS TO COMPLY WITH: 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING, AND |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |