| 2016-04-19 11:07:57 | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P1.1 THE TRENCH DRAIN SHOWS A SECOND PIPE |
| | CONNECTED TO IT NOT TIED TO OIL SEPARATOR . |
| | PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 2. ORIGINAL COMMENT STATES SHT.A2.0 - DETAIL #1 - THE |
| | DOORS TO RESTROOMS #213 & 214 CANNOT SWING INTO THE |
| | CLEA R FLOOR SPACE FOR THE LAVATORIES. 2014 FBC-ACCESS. |
| | SEC.603.2.3. (SEE EXCEPTION #2). 2ND REVIEW YOU SHOW |
| | COMPLIANCE WITH EXCEPTION IN BATHROOM 213 BUT NO IN 214 |
| | . |
| | PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 3.SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| | DIMENSION OF THE ACCESSIBLE STALL IN THE WOMEN'S |
| | RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS |
| | FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE |
| | WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE |
| | CENTERLINE OF THE WATER CLOSET. 2ND REQUEST |
| | |
| | 4. SHT. A10.1 THE TOP OF URINAL SCREEN SHOWS 56IN. |
| | ABOVE FF IT SHALL BE A MIN. OF 60IN. |
| | PER FBC SEC. 1210.3.2 |
| | |
| | 5. SHT. P1.1 RM # 171 |
| | (A) PROVIDE PIPING DIAGRAM FOR M OIL MANAGEMENT |
| | CONTROLLER |
| | (B) THE TANKS THAT ARE LABELED M ARE THEY FOR STORAGE |
| | OF OIL MEASURED IN GALLONS PLEASE CLARIFY. |
| | (C) WHAT ARE H AND K FOR PLEASE CLARIFY. |
| | (D) IT APPEARS THAT THE PARTS WASHER IS LABELED AS M |
| | FOR OIL MANAGEMENT CONTROLLER PLEASE CLARIFY |
| | (E) PROVIDE PIPING DIAGRAM FOR BLOWER LABELED P. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 6. THE STACK FOR THE SINK ON THE 5TH FLOOR IS SHOWN ON |
| | P1.3 AS A 4IN. ON SHT. P2.1 IT IS SHOWN AS 2IN. |
| | PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 7. SHT. P0.1 THE SPECS GIVEN FOR OIL SEPARATOR DO NOT |
| | COMPLY WITH FBC PL SEC 1003.4.2.1. |
| | PROVIDE MANUFACTURE SPECS THAT COMPLY WITH FBC PL SEC |
| | 1003.4.2.1. |
| | |
| | 8. SHT. P0.3 THE CALCULATION GIVEN FOR OIL SEPARATOR DO |
| | NOT COMPLY WITH FBCPL SEC 1003.4.2.2 IT APPEARS THAT |
| | YOU MIGHT HAVE USED CALCULATION FOR SIZING A GREASE |
| | INTERCEPTOR. |
| | PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 9. SHT. P1.2 SHOW A PLAN NOTE IN THE AREA RM # 115 AND |
| | 117 THAT INDICATES A WATER HEATER AND MOP SINK . |
| | PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 10. THE DIGITAL SIGNATURES ARE INVALID ON PLUMBING |
| | PAGES THEY SHALL COMPLY WITH FAC 61G15-23.003 |
| | |
| | |