| 2016-03-29 16:52:41 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15120536 |
| | 3/29/16 |
| | |
| | 1) 1ST REVIEW COMMENTS #1 & 2 STILL EXIST. PLEASE |
| | PROVIDE THE REVISED ENERGY CALCULATIONS AND INCLUDE |
| | COMPLIANCE DATA IN THE CALCULATIONS FOR THE NEW MS-6 & |
| | 7 SYSTEMS. |
| | 2) 1ST REVIEW COMMENT #4 STILL EXISTS. PLEASE NOTE THAT |
| | SYSTEMS THAT HAVE COOLING CAPACITIES GREATER THAN |
| | 65,000 BTUH MUST MEET THE MINIMUM EER NOT SEER- SEE |
| | TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. |
| | 3) THE NARRATIVE RESPONSE FROM THE EOR TO COMMENTS #5 & |
| | 6 INDICATE NATURAL AIR INFILTRATION IS TO BE USED TO |
| | PROVIDE THE REQUIRED O/A AIR FOR THE SYSTEMS, HOWEVER |
| | THESE SYSTEMS ARE ALSO PROVIDING THE MAKE-UP AIR FOR |
| | THE EXHAUST SYSTEMS- REFER TO SECTION 501.4 FBC-14 |
| | MECHANICAL WHICH STATES THAT THE CALCULATED BUILDING |
| | AIR INFILTRATION RATE SHALL NOT BE USED AS A COMPONENT |
| | OF A MAKE-UP AIR SYSTEM. |
| | 4) SHEET M0.3: A) THE MODEL NUMBER AND SENSIBLE BTU |
| | CAPACITY LISTED FOR AHU-4/CU-4 DO NOT APPEAR TO BE |
| | CORRECT. B) AHU-11/CU-11 SYSTEM SHOULD HAVE AN EER PER |
| | TABLE C404.2.3(1). |
| | 5) M1.0: THE SERVICE RECEPTION GARAGE REQUIRES AN |
| | EXHAUST SYSTEM PER SECTION 404.1 FBC-14 MECHANICAL. CO2 |
| | AND NO2 SENSORS ARE SHOWN ON THE PLANS, HOWEVER NO |
| | EXHAUST SYSTEM IS SHOWN, AND THERE IS NO EXHAUST FAN |
| | DESIGNATED FOR THAT AREA IN THE EQUIPMENT SCHEDULE. |
| | 6) M1.1: LABEL THE O/A INTAKE LOUVER FOR AHU-4 & 5. |
| | 7) COMMENT #14 FROM THE 1ST REVIEW HAS NOT BEEN |
| | COMPLETELY ADDRESSED. PLEASE PROVIDE THE REQUESTED |
| | EXHAUST CALCULATION ON THE PLAN, INDICATE THE TYPE AND |
| | SIZE (DIMENSIONS) OF THE MAKE-UP AIR INTAKE, AND |
| | PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE EOR. |
| | 8) COMMENT #15 STILL EXISTS: NEITHER THE MECHANICAL OR |
| | FIRE ALARM PLANS ARE INDICATING A SEQUENCE OF OPERATION |
| | FOR THE DUCT SMOKE DETECTORS. PLEASE REVIEW THE |
| | PREVIOUS COMMENT AND SHOW COMPLIANCE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |