| Date |
Text |
| 2016-03-31 08:00:00 | 2ND ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | PENDING COMMENTS: |
| | |
| | THE BELOW COMMENTS AS PREVIUOSLY STATED WILL REQUIRE |
| | AHJ APPROVAL, PLEASE MAKE ARRANGEMENTS TO CONTACT |
| | ROBERT BROWN (BO) OR DOUG HARVEY (ABO) |
| | ALL OTHER COMMENTS ADDRESSED EXCEPT THE BELOW INITIAL |
| | REVIEW COMMENTS |
| | |
| | |
| | 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS |
| | MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A. |
| | ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY |
| | ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH |
| | 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE |
| | SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL |
| | PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH |
| | IS SUBJECT TO APPROVAL. |
| | 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO |
| | BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13. |
| | SEE ABOVE. |
| | 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS |
| | TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS |
| | NOTED IN COMMENT #13. SEE ABOVE. |
| | 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC |
| | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF |
| | THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170. |
| | ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE |
| | EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION |
| | OF EGRESS. A NOTE WILL SUFFICE. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |