| 2016-01-19 09:49:15 | 1) PROVIDE MATCH LINES FOR THE PLUMBING PLAN VIEW |
| | DRAWINGS. IT IS DIFFICULT TO FOLLOW THE CONTINUATION OF |
| | THE PLUMBING SYSTEM FROM ONE SHEET TO THE NEXT.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 2) CLARIFY THE OCCUPANCY TYPE THAT YOU ARE USING TO |
| | CALCULATE THE REQUIRED PLUMBING FIXTURES FOR THE |
| | PORSCHE & BENTLEY AREAS. |
| | 3) THE ARCHITECTURAL PLANS HAVE THE DIFFERENT AREAS |
| | LABELE "A - F" AND THE PLUMBING PLANS ARE LABELED BY |
| | THE AREA NAME ( PORSCHE-SOUTH, PORSCHE-NORTH, ROLLS |
| | ROYCE/BENTLEY ETC.). IT IS EXTREMELY DIFFICULT TO |
| | REVIEW THESE PLANS WITHOUT CORRELATING NAMING |
| | CONVENTIONS. PLEASE ATTEMPT TO CORRELATE THE |
| | IDENTIFICATION OF THESE PLANS IN A MANNER THAT MAKES IT |
| | EFFICIENT TO PERFORM A COMPREHENSIVE REVIEW. |
| | 4) THE TRENCH DRAINS LOCATED IN THE DETAIL AREA #166 |
| | SHALL DISCHARGE TO THE OIL INTERCEPTOR PER THE 2014 |
| | FBC-PLUMBING SEC.1003.4.2.2. |
| | 5) SHT. A1.1.1E - LOCKER ROOMS #125 & #126 SHOWS A |
| | HANDICAPPED ACCESSIBLE TOILET COMPARTMENT WITH A |
| | LAVATORY IN IT BUT NO WATER CLOSET. CLARIFY. 2014 |
| | FBC-ACCESS. SEC.213.3.1 & 604.8.1. |
| | 6) SHT. A1.1.1E - LOCKER RM. 3126 - SHOWS THE DOOR FOR |
| | THE ACCESSIBLE STALL SWINGING INTO THE CLEAR FLOOR |
| | SPACE FOR WHAT APPEARS TO BE AN ACCESSIBLE URINAL. THE |
| | DOOR CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| | FIXTURE PER 2014 FBC-ACCESS.SEC.603.2.3. |
| | 7) SHT. A1.2.1 - THE BREAK ROOM SINK IN ROOM #209 SHALL |
| | COMPLY WITH 2014 FBC-ACCESS. SEC.212 & 606. |
| | 8) SHT. A1.5.1 - TOILET ROOM # 500A - SHOW THE WIDTH OF |
| | THE TOILET ROOM ON DETAIL #2. THE MINIMUM WIDTH IS 85 |
| | INCHES. 86 INCHES ALLOWS FOR TOLERANCE. |
| | 9).SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL SINGLE |
| | USER TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT. A2.0 - DETAILS #2 & #4 - IDENTIFY THE |
| | HANDICAPPED ACCESSIBLE URINAL IN BOTH RESTROOMS. COMPLY |
| | WITH 2014 FBC - ACCESS. SEC.605. |
| | 11) SHT. A2.0 - SHOW THE FIXTURE CLEARANCE DIMENSION |
| | FROM THE CENTERLINE OF THE ACCESSIBLE WATER CLOSET TO |
| | THE SIDE WALL. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.2. |
| | 12) SHT.A2.0 - DETAIL #1 - THE DOORS TO RESTROOMS #213 |
| | & 214 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORIES. 2014 FBC-ACCESS. SEC.603.2.3. (SEE |
| | EXCEPTION #2). |
| | 13) SHT. A2.0 - SHOW THE FIXTURE CLEARANCES OF THE |
| | URINALS ON SHT. A2.0, DETAIL #2 AND ALSO DETAIL #4. |
| | .COMPLY WITH 2014 FBC-PLUMBING, SEC.405.3.1. |
| | 14) SHT. A2.1 - SHOW THE FIXTURE CLEARANCE FOR THE |
| | URINALS IN THE ENLARGED STAFF LOCKERS/RESTROOMS, DETAIL |
| | #2. COMPLY WITH 2014 FBC-PLUMBING SEC. 405.3.1. |
| | 15) SHT. A2.0 - DETAIL #4 - THE DRINKING FOUNTAINS |
| | SHALL CCOMPLY WITH 2014 FBC-ACCESS. SEC.307.2 FOR |
| | PROTRUDING OBJECTS. |
| | 16) SHT. A2.1 - DETAIL #2 - SHOW THE REQUIRED TURNING |
| | SPACE IN THE MEN'S & WOMEN'S RESTROOMS PER THE 2014 |
| | FBC- ACCESS. SEC.304.3.1. |
| | 17) SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| | DIMENSION OF THE ACCESSIBLE STALL IN THE WWOMEN'S |
| | RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS |
| | FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE |
| | WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE |
| | CENTERLINE OF THE WATER CLOSET. |
| | 18) SHT. A10.1 - THE URINAL SCREEN SHALL EXTEND NOT |
| | LESS THAN 60 INCHES ABOVE THE FINISH FLOOR.2014 FBC |
| | SEC. 1210.3.2. |
| | 19) SHT. A10.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE |
| | UNDER THE LAVATORY IN DETAIL #7. COMPLY WITH 2014 |
| | FBC-ACCESS. SEC.305, 306. |
| | 20) SHT.A10.3 - DETAILS #7 & #8 - THE HEIGHT OF THE |
| | WATER CLOSET IS SHOWN AS 15 INCHES ABOVE THE FINISH |
| | FLOOR. THE HEIGHT OF THE ACCESSIBLE WATER CLOSET SHALL |
| | BE BETWEEN 17" & 19 " ABOVE THE FINISH FLOOR. 2014 FBC- |
| | ACCESS. SEC.604.4. |
| | 21) SHT. A10.7 - DETAIL #6 - THE URINAL LIP IS SHOWN AS |
| | 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A HANDICAPPED |
| | URINAL, THE MAX. HEIGHT TO THE URINAL LIP SHALL BE 17 |
| | INCHES. FBC-ACCESS. SEC. 605.2. |
| | 22) SHT.A10.7 - DETAIL # 16 - THE URINAL LIP IS SHOWN |
| | AS 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A |
| | HANDICAPPED URINAL, THE MAX. HEIGHT TO THE URINAL LIP |
| | SHALL BE 17 INCHES. FBC-ACCESS. SEC. 605.2. |
| | 23) SHT. P1.1 - IDENTIFY ALL THE EQUIPMENT & TANKS IN |
| | ROMM #171. WPB AMEND. TO FBC SEC.107.2.1. |
| | 24) SUBMIT A PIPING RISER FOR THE COMPRESSED AIR |
| | SYSTEM.WPB AMEND. TO FBC SEC.107.2.1. |
| | 25) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB |
| | AMEND. TO FBC SEC.107.2.1. |
| | 26) CLEARLY SHOW THE DRAIN LINES FROM THE ELEVATOR |
| | SUMPS TO THE OIL WASTE SYSTEM ON THE PLUMBING RISER.WPB |
| | AMEND. TO FBC SEC.107.2.1. |
| | 27) SHT.P2.2 - MEN'S & WOMEN'S TOILET ROOMS #154 & #155 |
| | - THE CIRCUIT VENT SHALL BE LOCATED BETWEEN THE THE TWO |
| | MOST UPSTREAM FIXTURE DRAINS. AS DRAWN, THE VENT IS |
| | LOCATED DOWNSTREAM OF THE TWO MOST UPSTREAM WATER |
| | CLOSETS.2014 FPC SEC.914.2. |
| | 28) SHT. P2.1 - SANITARY RISER #2 - TECH RESTROOMS - |
| | SIZE THE VENTS FOR THE URINALS. |
| | 29) SHT. P2.1 - RISER #1 - ROLLS ROYCE/BENTLEY - TWO |
| | LAVATORIES ARE SHOWN ON THE SANITARY RISER FOR ROOM |
| | #126 AND ONLY ONE IS SHOWN ON SHT. P1.3. CLARIFY. |
| | 30) SHT.P1.3 SHOWS A 4"SANITARY RISER ON COLUMN LINE BB |
| | BETWEEN COLS. #7 & #8 BUT IS NOT SHOWN ON THE SANITARY |
| | RISER SHT. P2.1.. CLARIFY. |
| | 31) SHT.P1.3 - SHOWS A SANITARY BRANCH FROM THE |
| | BUILDING DRAIN GOING OVER TO STAIR #2 WITH A NOTE " 2" |
| | SANITARY FROM ABOVE" BUT IT IS NOT SHOWN ON SHT. P2.1, |
| | RISER #1(ROLLS ROYCE/BENTLEY0. CLARIFY. |
| | 32) SHT. P1.6 - THE DISCHARGE FROM THE WASH BAYS SHALL |
| | DISCHARGE THROUGH THE OIL SEPARATOR. 2014 FPC SEC. |
| | 1003.4. |
| | 33) SHT.P2.4 - WATER RISER #5 - HOT WATER IS REQUIRED |
| | TO THE MOP SINK IN ROOM #156. 2014 FBC SEC.607.1. |
| | 34) SHT.P0.3 - PROVIDE THE DIMENSIONS OF THE OIL |
| | SEPARATOR.THE OIL SEPARATOR SHALL BE SIZED IN |
| | ACCCORDANCE WITH THE 2014 FPC SECS. 1003.4.2, |
| | 1003.4.2.1, 1003.4.2.2. |
| | 35) SHT.P1.0 - THE DRINKING FOUNTAINS ARE SHOWN ON THE |
| | FLOOR PLAN BUT ARE NOT SHOWN ON THE WATER RISER ON SHT. |
| | P2.4 (RISER #5 RESTROOMS #154 & 155 ) . CLARIFY. |
| | 36) SHT.P1.0A - DRINKING FOUNTAINS IN PASSAGE AREA #206 |
| | ARE SHOWN ON THE FLOOR PLAN BUT NOT ON THE WATER RISER |
| | ON SHT.P2.4. CLARIFY.SEE AREA BY COLS.15 & 0.2. |
| | 37) SHT. P2.3 - HOT WATER IS REQUIRED TO THE MOP SINK |
| | BY STORAGE ROOM #116. 2014 FPC SEC.607.1. |
| | 38) SHT. P1.2 - THE PLAN VIEW FOR THE AREA NEAR STORAGE |
| | ROOM #116 DOES NOT CORRELATE WITH SHT. A1.1. CLARIFY. |
| | 39) SHT.P2.5 - THE MAXIMUM SQUARE FOOTAGE TO BE DRAINED |
| | BY AN 8" HORIZONTAL DRAIN IS 9200 SQ. FT.PER 2014 FBC |
| | TABLE 1106.3. RISER S-1 SHOWS AN 8" DRAIN DRAINING |
| | 11,500 SQ. FT. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |