| 2016-01-19 10:38:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120536 |
| | ADD: 2745 OKEECHOBEE BLVD. |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-568-8931 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 15/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | |
| | 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM |
| | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS, |
| | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. |
| | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) SHEET 011-INDEX INDICATES SHEETS 028-LS-1W, |
| | 029-LS-2E, 030-LS-2W, 033-A0.1 & 034-A1.1.1 ARE |
| | MISSING, WERE NOT PART OF THIS SUBMITTAL. A THOROUGH |
| | REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE |
| | ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4) PLEASE PROVIDE A SOILS REPORT IN COMPLIANCE WITH: |
| | 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 5) SHEET 027-LS-1E: |
| | 5A) THE PLAN DOES SHOW EXIT DIRECTIONAL AND EXIT |
| | LIGHTS, BUT THE PLAN DOES NOT PROVIDE A EGRESS PATH, |
| | INCLUDING MEZZANINE OCCUPANT LOADS, ALLOWABLE OCCUPANT |
| | LOAD FOR STAIRS PER FBC-B 1005.3.1 AND AS TO WHICH |
| | DOORS THEY WILL EXIT AND THE ALLOWABLE OCCUPANT LOAD |
| | PER SET OF DOORS PER FBC-B 1005.3.2. |
| | |
| | 5B) THE SERVICE VESTIBULE SHOWS THE USE OF A PLATFORM |
| | LIFT, PLEASE PROVIDE THE MANUFACTURERS SHOP DRAWINGS |
| | AND OR SPEC SHEET THAT SHOWS THE LIFT COMPLIES WITH |
| | ASME A18.1 (FBC-ACCESSIBILITY CODE 410.1). |
| | |
| | 5C) THERE IS AN AREA OF CONCERN, THE DRIVEWAY 170 |
| | APPEARS TO BE A DUAL USE LOADING ZONE FOR THE PARTS |
| | RECEIVING ROOM 163. THE ISSUE IS BOTH ROOMS THE PARTS |
| | RECEIVING DOOR AND ROOM 166 DETAIL ROOM BOTH SHOW THE |
| | EXTERIOR DOOR IS THE EXIT DISCHARGE THAT LEADS INTO A |
| | COURTYARD AREA THAT IS NOT PROTECTED AS REQUIRED BY |
| | SECTION 1027.4, 1027.4.1 & 1027.4.2 THAT WILL ALLOW THE |
| | OCCUPANT TO TRAVEL TO THE PUBLIC WAY. OCCUPANT LOADS |
| | FOR THESE DOORS HAS NOT BEEN DECLARED SO THE REQUIRED |
| | WIDTH OF THE EGRESS PATH CANNOT CURRENTLY BE |
| | DETERMINED. |
| | 5D) THE MEZZANINE LEVEL IS NOT SHOWN ON THE 1ST FLOOR |
| | LIFE SAFETY PLAN, ALTHOUGH IT IS NOT ANOTHER STORY SEE |
| | 054-A1-2-1A. IT APPEARS THERE ARE 2 MEZZANINES, ONE |
| | OVER THE BUSINESS OCCUPANCY THE OTHER IN THE PARTS |
| | STORAGE AREA. THE MEZZANINE LEVEL OVER THE BUSINESS |
| | OCCUPANCY DOES HAVE WHAT APPEARS TO BE A ELEVATOR TO |
| | GET A WHEEL CHAIRED CLIENT OR WORKER TO THE UPPER |
| | PORTION OF THE MEZZANINE BUT THERE ARE STAIRS DOWN TO |
| | THE CONFERENCE ROOM. NO ACCESSIBILITY TO THE CONFERENCE |
| | ROOM. |
| | 2014 FBC-B 201.1.1VERTICAL ACCESSIBILITY. 201.1.1 |
| | VERTICAL ACCESSIBILITY. SECTIONS 553.501-553.513, F.S., |
| | AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO NOT |
| | RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR |
| | FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND |
| | BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER |
| | THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN |
| | SUCH BUILDING, STRUCTURE OR FACILITY. |
| | |
| | 203.9 EMPLOYEE WORK AREAS. |
| | SPACES AND ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL |
| | ONLY BE REQUIRED TO COMPLY WITH 206.2.8, 207.1, AND |
| | 215.3 AND SHALL BE DESIGNED AND CONSTRUCTED SO THAT |
| | INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND |
| | EXIT THE EMPLOYEE WORK AREA. |
| | |
| | 5E) SHEET 054-A1-2-1A. THE QUESTION ARISES IS THE |
| | ELEVATOR ON EMERGENCY POWER? HOW WILL WHEELCHAIR BOUND |
| | PERSON GET BACK DOWN FROM THE MEZZANINE IN CASE OF LOSS |
| | OF POWER? . 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS |
| | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY. |
| | |
| | 6) SHEET 036-A1-1-1B PARTS STORAGE IS THERE A MEZZANINE |
| | LEVEL IN THE PARTS STORAGE OR A OPEN GRID SECOND FLOOR? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7A) SHEET 036-A1-1-1B INDICATES A TIRE CAROUSEL, PLEASE |
| | PROVIDE MANUFACTURES SPECIFICATIONS AND CUT SHEETS ON |
| | THIS EQUIPMENT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 7B) PLEASE PROVIDE THE CUBIC FEET THE TIRE CAROUSEL |
| | ENCLOSES, MAY NEED TO COMPLY WITH 903.2.9.2 BULK |
| | STORAGE OF TIRES. |
| | |
| | 8) SHEET 036-A1-1-1B SERVICE BAY INDICATES THE USE OF |
| | CAR LIFTS WILL THESE LIFTS BE USING A HYDRAULIC TYPE |
| | LIFT? IS SO PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B |
| | SECTION B 3011.1 ELECTROLYSIS PROTECTION FOR |
| | UNDERGROUND HYDRAULIC ELEVATOR CYLINDERS. ALL NEWLY |
| | INSTALLED UNDERGROUND HYDRAULIC PRESSURE CYLINDERS |
| | SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT TO |
| | MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL |
| | CYLINDER AND GROUND CATHODE. |
| | |
| | 9) SHEET 145-S1.1A IN THE BOTTOM RIGHT SHOWS A KEY |
| | FOUNDATION PLAN FOR THE FOUNDATION. THE KEY PLAN DOES |
| | NOT IDENTIFY THE FOUNDATION BEHIND THE BUILDING LABELED |
| | 1. PLEASE PROVIDE WHERE THIS PLAN CAN BE LOCATED. |
| | |
| | 10) SHEET 037-A1-1-1C INDICATES AN ELEVATOR DETAIL |
| | FOUND ON 109-A7-1 INDICATING THE ELEVATOR TO THE 6TH |
| | FLOOR/ ROOF TOP OF THE GARAGE AND SHEET 111-A7-3 BOTH |
| | APPEAR TO BE A HYDRAULIC TYPE ELEVATOR . |
| | PLEASE PROVIDE CODE COMPLIANCE WITH 2014 FBC-B 3011.1 |
| | ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC |
| | ELEVATOR CYLINDERS. ALL NEWLY INSTALLED UNDERGROUND |
| | HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER |
| | PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION |
| | BETWEEN THE METAL CYLINDER AND GROUND CATHODE. |
| | |
| | 11) SHEET 036-A1-1-1B THE CAR LIFTS DO NOT INDICATE IF |
| | THE CAR LIFTS ARE A HYDRAULIC TYPE OF ELEVATOR |
| | REQUIRING COMPLIANCE WITH 2014 FBC-B 3011.1 |
| | ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC |
| | ELEVATOR CYLINDERS. |
| | |
| | 12) SHEET 037-A1-1-1C NOR THE SHEET 109-A7-1 SHOW THE |
| | CAB OF ELEVATOR # 1 ACCOMMODATES THE AMBULANCE |
| | STRETCHER REQUIREMENTS OF FBC-B 3002.4. |
| | |
| | 13) SHEET 109-A7-1 WILL ALSO NEED TO PROVIDE COMPLIANCE |
| | WITH FBC-B 3004.2 & 3004.3 VENTING. |
| | |
| | 14A) SHEET 109-A7-1 SHOWS ELEVATOR # 1 AS THE VERTICAL |
| | ACCESSIBILITY FOR THE PARKING GARAGE FLOORS. |
| | IS THE ELEVATOR # 1 TIED TO EMERGENCY POWER TO BE |
| | CONSIDERED RELIABLE MEANS OF EGRESS IF THE POWER FAILS. |
| | MISSING THE LIFE SAFETY SHEET FOR THE 2ND FLOOR BUT FOR |
| | THE 3RD THROUGH THE 6TH FLOOR THE OCCUPANT LOAD IS 259 |
| | PER FLOOR. 2014 FBC-B SECTION 1021.2 REQUIRES AT LEAST |
| | 2 EXITS FROM EACH STORY OR OCCUPIED ROOF. |
| | THE 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS |
| | OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007. |
| | 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS |
| | REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT |
| | LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. PLEASE |
| | PROVIDE WHAT WILL BE CONSIDERED THE SECOND MEANS OF |
| | ACCESSIBLE EGRESS FOR THE PARKING GARAGE LEVELS |
| | 2THROUGH 6. |
| | |
| | 14B) THE PARKING GARAGE. THE PLANS DO NOT INDICATE THE |
| | USE OF THE PARKING GARAGE OTHER THAN THE STORAGE OF |
| | CARS. THE PLANS WILL NEED TO CLARIFY IF THE PARKING |
| | GARAGE IS STRICTLY FOR INVENTORY OF CARS, OR IF BOTH |
| | INVENTORY OF CARS AND CUSTOMER PARKING? THE QUESTION |
| | ARISES DOES THE REQUIREMENT FOR ACCESSIBLE PARKING |
| | SPACES FOR THE PUBLIC WITH ACCESS AISLES COME INTO PLAY |
| | AS WELL AS HEIGHT REQUIREMENTS FOR VAN PARKING. |
| | 2014 FBC-ACCESSIBILITY CODE 208.3.1, & 502.1 THROUGH |
| | 502.7 EVEN THOUGH THE PARKING GARAGE MAYBE STRICTLY |
| | USED JUST FOR THE INVENTORY OF AUTOMOBILES. |
| | PLEASE REVIEW SECTION FBC-ACCESSIBILITY CODE 208.1 |
| | REQUIREMENTS FOR VAN PARKING STRUCTURES. EXCEPTION: |
| | PARKING SPACES USED EXCLUSIVELY FOR BUSES, TRUCKS, |
| | OTHER DELIVERY VEHICLES, LAW ENFORCEMENT VEHICLES, OR |
| | VEHICULAR IMPOUND SHALL NOT BE REQUIRED TO COMPLY WITH |
| | 208 PROVIDED THAT LOTS ACCESSED BY THE PUBLIC ARE |
| | PROVIDED WITH A PASSENGER LOADING ZONE COMPLYING WITH |
| | 503. |
| | |
| | 14C) SHEET 090-A4-4 DETAILS 1 & 2 BOTH PROVIDE |
| | ELEVATIONS FOR THE FINISH FLOOR ON VARIOUS FLOOR LEVELS |
| | AND DETAIL # 1 INDICATES THE FLOOR STRUCTURAL MEMBERS |
| | ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD PROVIDE |
| | AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST, DEPENDING |
| | ON THE LAYOUT OF THE RAINWATER HORIZONTAL RUNS AND FIRE |
| | SPRINKLER LAYOUT WHICH HAS NOT YET BEEN PROVIDED.2014 |
| | FBC-B 406.4.1. |
| | |
| | 15A) SHEET 079-A3-0 HEADING PARKING GARAGE CALCULATIONS |
| | PLEASE ADD AN ADDITIONAL COLUMN PER 2014 |
| | FBC-B SECTION 406.2. THE AREA OF SUCH OPENINGS IN |
| | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| | |
| | 15B) IN THE 2014 FBC-B SECTION 406.5.2 THE CODE ALSO |
| | REQUIRES THE INTERIOR WALLS SHALL BE NOT LESS THAN 20 |
| | PERCENT OPEN WITH UNIFORMLY DISTRIBUTED OPENINGS. |
| | PLEASE ADD ANOTHER COLUMN TO THE HEADING PARKING GARAGE |
| | CALCULATIONS SHOWING CODE COMPLIANCE. |
| | 16A) SHEET 026-LS-0-1 UNDER THE HEADING OF APPLICABLE |
| | CODES INDICATES THIS BUILDING IS TO BE A 1B TYPE OF |
| | CONSTRUCTION. FULLY SPRINKLERED BUILDING. THE INDEX |
| | SHEET 001 DOES NOT INDICATE ANY FIRE SPRINKLER PLANS TO |
| | BE INCORPORATED WITHIN THE SET OF DRAWINGS. THE PLANS |
| | SHEET 026-LS-0.1 INDICATES AREA INCREASES WERE TAKEN |
| | FOR FIRE SPRINKLERING OF THE WHOLE BUILDING. |
| | |
| | 16B) SHEETS 108-A7-0 STAIR 3 (ASSUMED STAIR 2 IS ALIKE |
| | BUT OPPOSITE) SHOWS FLOOR PLAN VIEW AS WELL AS A CUT |
| | SECTION THROUGH THE STAIR TOWER BUT THERE IS NO MENTION |
| | OR DETAILS OF HOW THE OPEN PARKING GARAGE IS GOING TO |
| | BE FIRE SPRINKLERED AS WELL AS THE 6TH FLOOR OR ROOF |
| | LEVEL. THIS LEVEL IS OCCUPIED (USABLE) SPACE AND |
| | CONSIDERED A STORY? THE PLANS DO NOT PROVIDE A STAND |
| | PIPE IN ANY OF THE STAIR TOWERS, 1,2 OR 3. SEE 2014 |
| | FBC-B 406.5.8. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (5.) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | RISER DIAGRAM |
| | |
| | 17) SHEET 109-A7-1 ALSO IS LACKING THE REQUIRED |
| | STANDPIPE WITHIN THE STAIRWELL AND HOW THE UPPER LEVEL |
| | THE 6TH FLOOR/ ROOF TOP PARKING LEVEL WILL ACHIEVE CODE |
| | COMPLIANCE. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (5.) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | RISER DIAGRAM |
| | |
| | 18A) PLEASE SHOW WHERE THE PLANS CAN SHOW COMPLIANCE |
| | WITH THE 2014 FBC-B SECTION 406.4.3 VEHICLE BARRIERS. |
| | VEHICLE BARRIERS NOT LESS THAN 2 FEET 9 INCHES (835 MM) |
| | IN HEIGHT SHALL BE PLACED AT THE ENDS OF DRIVE LANES, |
| | AND AT THE END OF PARKING SPACES WHERE THE VERTICAL |
| | DISTANCE TO THE GROUND OR SURFACE DIRECTLY BELOW IS |
| | GREATER THAN 1 FOOT (305 MM). VEHICLE BARRIERS SHALL |
| | COMPLY WITH THE LOADING REQUIREMENTS OF SECTION |
| | 1607.8.3. |
| | |
| | 18B) PLEASE SHOW WHERE THE PLANS CAN SHOW COMPLIANCE |
| | WITH THE 2014 FBC-B SECTION 406.4.2 GUARDS. |
| | GUARDS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 1013. GUARDS SERVING AS VEHICLE BARRIERS SHALL COMPLY |
| | WITH SECTIONS 406.4.3 AND 1013. |
| | |
| | 19) THIS COMMENT IS COMMON FOR ALL FLOORS. SHEET |
| | 055-A1-2-B THE FLOOR INDICATES THE ELEVATION OF THE |
| | LEVEL FLOOR AT 38.0 FEET. THE PLANS DO SHOW WHAT |
| | APPEARS TO BE FLOOR DRAINS BUT THE DIFFERENCE IN |
| | ELEVATION IS NOT MARKED ON THE PLANS NOR IS THERE ANY |
| | NOTES ON THE PLANS INDICATING THE DIFFERENCE IN |
| | ELEVATION. PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| | FBC-B 406.4.5 FLOOR SURFACE. |
| | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR |
| | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | |
| | 20) PORTIONS OF THE 1ST FLOOR AND 2ND FLOOR ARE |
| | CONSIDERED AN ENCLOSED PARKING GARAGE, PLEASE IDENTIFY |
| | WHERE IN EITHER THE ARCHITECTURAL SHEETS OR THE |
| | MECHANICAL SHEETS COMPLIANCE WITH 2014 FBC-B 406.6.2 |
| | VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE |
| | PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL. |
| | |
| | 21) PLEASE PROVIDE WHERE IN THE SUBMITTED PLANS |
| | COMPLIANCE WITH FBC-B SECTION [F] 406.6.3 AUTOMATIC |
| | SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE |
| | EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.2.10. |
| | |
| | 22) PLEASE PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION |
| | 406.8.2 VENTILATION. REPAIR GARAGES SHALL BE |
| | MECHANICALLY VENTILATED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL. THE VENTILATION SYSTEM SHALL |
| | BE CONTROLLED AT THE ENTRANCE TO THE GARAGE. |
| | |
| | 23) PLEASE PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION |
| | 406.8.6 AUTOMATIC SPRINKLER SYSTEM. |
| | A REPAIR GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.9.1. |
| | |
| | 24) SHEET 038-A1-1-1D. NEXT TO STAIR 128 THE PLANS |
| | INDICATE THE USE OF A PLATFORM LIFT, PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE 410.1 |
| | THROUGH 410.6. |
| | |
| | 25) SHEETS 035-A1.1.1A THROUGH 040-A1.1.1F, AND SHEET |
| | 113-A8.0 DOOR SCHEDULE: |
| | |
| | 25A) DOOR TYPE (N) SHOW THEY ARE A HORIZONTAL |
| | BI-PARTING DOOR. SHEET 113-A8-0 INDICATES A DOOR TYPE |
| | (N) BUT DOES NOT INDICATE TO WHICH CODE SECTION THE |
| | DOORS ARE COMPLY 1008.1.4.2 POWER OPERATED DOORS OR |
| | 1008.1.4.3 HORIZONTAL SLIDING DOORS OR HOW MUCH FORCE |
| | IS TO BE APPLIED TO SET THE DOOR IN MOTION. DOORS SHALL |
| | BE OPENABLE BY A SIMPLE METHOD FROM BOTH SIDES WITHOUT |
| | SPECIAL KNOWLEDGE OR EFFORT, HOW WILL THIS BE |
| | ACCOMPLISHED. |
| | |
| | 25B) SHEET 039-A1-1-1E DOOR 121 IS IDENTIFIED ON THE |
| | PLAN AS A SLIDING GLASS DOOR. SHEET 113-A8-0 INDICATES |
| | THIS DOOR TYPE AS DOOR TYPE ( E ), WHICH IS A SWING |
| | TYPE OF DOOR. 107.2.1.3 IT APPEARS TO BE A TYPO, |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 26) SHEET 100-A6-2 PLEASE PROVIDE HOW THE SKYLIGHT |
| | GLAZING IS GOING TO COMPLY WITH THE 2014 FBC-B 2405.2 |
| | ALLOWABLE GLAZING MATERIALS AND LIMITATIONS. |
| | 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES. |
| | UNIT SKYLIGHTS AND TUBULAR DEVICES SHALL BE TESTED AND |
| | LABELED AS COMPLYING WITH AAMA/WDMA/CSA 101/I.S./A440. |
| | THE LABEL SHALL STATE THE NAME OF THE MANUFACTURER, THE |
| | APPROVED LABELING AGENCY, THE PRODUCT DESIGNATION AND |
| | THE PERFORMANCE GRADE RATING AS SPECIFIED IN |
| | AAMA/WDMA/CSA 101/I.S.2/ A440. IF THE PRODUCT |
| | MANUFACTURER HAS CHOSEN TO HAVE THE PERFORMANCE GRADE |
| | OF THE SKYLIGHT RATED SEPARATELY FOR POSITIVE AND |
| | NEGATIVE DESIGN PRESSURE, THEN THE LABEL SHALL STATE |
| | BOTH PERFORMANCE GRADE RATINGS AS SPECIFIED IN |
| | AAMA/WDMA/ CSA 101/I.S.2/A440 AND THE SKYLIGHT SHALL |
| | COMPLY WITH SECTION 2405.5.2. IF THE SKYLIGHT IS NOT |
| | RATED SEPARATELY FOR POSITIVE AND NEGATIVE PRESSURE, |
| | THEN THE PERFORMANCE GRADE RATING SHOWN ON THE LABEL |
| | SHALL BE THE PERFORMANCE GRADE RATING DETERMINED IN |
| | ACCORDANCE WITH AAMA/WDMA/CSA 101/ I.S.2/A440 FOR BOTH |
| | POSITIVE AND NEGATIVE DESIGN PRESSURE AND THE SKYLIGHT |
| | SHALL CONFORM TO SECTION 2405.5.1. |
| | |
| | 27) SHEET 140-S0.1 STRUCTURAL SPECIFICATION NOTES MISC. |
| | NOTE # 6 IS THE WIND DESIGN CRITERIA, PLEASE ALSO |
| | PROVIDE AT WHAT MEAN ROOF HEIGHT IS THE PRESSURES FOUND |
| | ON SHEET 143-S0.4 TAKEN? UNTIL THE MEAN ROOF HEIGHT IS |
| | GIVEN THE PRESSURES CANNOT BE VERIFIED. 2014 FBC-B |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF |
| | EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE |
| | ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR |
| | ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 |
| | RAD). |
| | |
| | |
| | 28) PLEASE PROVIDE THE PRESSURES FOUND ON SHEET |
| | 143-S0.4 IN VASD SINCE ALL OF THE PRODUCT APPROVALS ARE |
| | IN VASD. THE INSPECTORS ON SITE WILL BE LOOKING FOR THE |
| | PRESSURES ON THE S0,4 SHEET TO BE INLINE WITH THE |
| | PRODUCT APPROVALS. 1609.3.1 WIND SPEED CONVERSION VULT |
| | TO VASD. |
| | |
| | 29A) PLEASE SUBMIT PRODUCT APPROVALS TO COMPLY WITH: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING, AND |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 29B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 29C) THE CONTRACTOR OR DESIGNER OF RECORD MAY ELECT TO |
| | : 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 30A) PLEASE PROVIDE COMPLIANCE WITH:2014 FBC-B 1013.6 |
| | MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE |
| | APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS OR |
| | OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED |
| | WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF |
| | A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED |
| | MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR |
| | GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO |
| | PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN |
| | DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30 |
| | INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE, |
| | EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 30B) 2014 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE |
| | PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN |
| | 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A |
| | WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED |
| | MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR |
| | GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO |
| | PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN |
| | DIAMETER. |
| | |
| | 30C) 2014 FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS. |
| | MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| | THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| | ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| | THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| | SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | FIRE-RESISTANCE RATING REQUIREMENTS. |
| | |
| | 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 32) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |