| 2016-02-12 15:50:45 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15120534 |
| | 2/12/16 |
| | |
| | 1) AS STATED IN THE LETTER FROM MR. HUMBERTO DIAZ |
| | R403.6.1 EQUIPMENT SIZING. |
| | "HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS." THE SUBMITTED REVISED CALCULATION |
| | DOES NOT PROVIDE LOADS BASED ON THE DIRECTIONAL |
| | ORIENTATION OF THE BUILDING, DOES NOT IDENTIFY THE |
| | PROJECT, PROJECT ADDRESS,MANUFACTURER AND MODEL NUMBER |
| | OF THE EQUIPMENT, AND THE PERSON WHO PREPARED THE |
| | CALDCULATION. THE LETTER STATES THAT THE CALCULATION |
| | METHOD USED IS THE CARRIER HAP SOFTWARE PROGRAM HOWEVER |
| | THAT TITLE DOES NOT APPEAR ANYWHERE ON THE DOCUMENT. AS |
| | PREVIOULSY REQUESTED, PLEASE PROVIDE MANUAL J |
| | CALCULATIONS USING AN APPROVED SOFTWARE PROGRAM. |
| | 2) THE AC CLOSET SIZE IS NOT IN COMPLIANCE WITH SECTION |
| | M1305.1.1 WHICH REQUIRES THE ENCLOSING SPACE TO BE AT |
| | LEAST 12 IN. WIDER THAN THE WIDTH OF THE AIR HANDLER. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |