Plan Review Notes
Plan Review Notes For Permit 15120533
Permit Number 15120533
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-29 10:17:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 315120533
 1/29/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS ON THE SECOND FLOOR AND IN THE COTTAGE- SEE
 SECTION R403.6 FBC-14 ENERGY CONSERVATION.
 2) PLEASE REVIEW SECTION R403.2.4 FBC-14 ENERGY
 CONSERVATION IN REGARD TO AHU-1 IN THE ATTIC, AND
 SUBMIT PERFORMANCE BASED ENERGY CALCULATIONS AND REVISE
 THE PLAN TO SHOW COMPLIANCE: R403.2.4 AIR-HANDLING
 UNITS.
 AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE
 AIR-CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM
 IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A
 DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN
 IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT
 THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT
 WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO
 AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU
 ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE
 EACH SEASON OF PEAK OPERATION.
 3) THE 8" TRANSFER DUCTS FROM BEDROOM 2 & 3 ARE
 UNDERSIZED PER SECTION M1602.4. PLEASE PROVIDE MINIMUM
 9" DUCTS FOR COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER