| Plan Review Notes For Permit 15120508 |
| Permit Number |
15120508 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-16 15:22:35 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PROVIDE LOAD CALCS. | | | | | | 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY | | | HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS | | | SHALL | | | BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. | | | SUCH A | | | DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE | | | BUILDING | | | OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL | | | CALCULATED | | | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS | | | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND | | | FACTORS, | | | AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED. | | | | | | | | | SPOKE TO FPL ENGINEER HE STATED ONLY 1 SERVICE DROP AT | | | LOT. |
|