| Plan Review Notes For Permit 15120461 |
| Permit Number |
15120461 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-16 09:57:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFICIENT DETAIL PROVIDED TO REVIEW AND/OR | | | APPROVE THIS PERMIT. | | | | | | 1. THE SUBMITTED PALNS SHALL COMPLY WITH FS 61G - 32 | | | WHERE APPLICABLE. | | | | | | 2. A DETAILED FLOOR PLAN INDICATING THE LOCATION OF THE | | | DEVICES IS NOT INCLUDED. | | | | | | 3. THE WORK DESCRIPTION INDICATES "INSTALL". PLEASE | | | PROVIDE ALL ELECTRICAL DETAILS IN COMPLIANCE WITH NFPA | | | 70 AND 72. | | | | | | 4. PROVIDE DETAILS ON THE DEVICES SUPPLIED BY THIS | | | INSTALLTION AND ALL BATTERY AND VOLTAGE DROP | | | CALCULATIONS. |
|