2016-01-06 14:20:17NOTICE TO INSPECTOR: PER FPL 480 V. IS NOT AVAILABLE IN
 THE AREA, THEREFORE DESIGN REVISED FOR 240 V. SEE VD
 CALCS. PERFORMANCE NOT AFFECTED BY VOLTAGE DECREASE.THE
 EC PRODUCED AN EMAIL FROM FPL INDICATING THE AVAILABLE
 VOLTAGE BEING 240 AS INDICATED. VOLTAGE DROP CALCS WERE
 PRODUCED AND VERIFIED FOR COMPLIANCE.