| Plan Review Notes For Permit 15120393 |
| Permit Number |
15120393 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-16 13:11:55 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | ALTERNATE CONTACT | | | | | | | | | NEC 230.23 A SERVICE CONDUCTORS SHALL HAVE SUFFICIENT | | | AMPACITY TO CARRY CURRENT FOR THE LOAD AS CACULATED IN | | | ACCORDANCE WITH ARTICLE 220. | | | BOTH YOUR DEMAND LOADS ADD UP TOO 184 AMPS ( 92 + 92 ) | | | , THEREFORE A 150 AMP SERVICE IS NON-COMPLIANT MUST | | | UPGRADE TO 200 OR RECALCULATE TO MATCH | | | EXISTING RISER DIAGRAM. TABLE 310.16 B7 SHOWS 1/0 AWG | | | IS GOOD FOR 175 AMPS NOT ENOUGH FOR LOAD CAPACITY. | | | | | | THE GROUNDING DETAIL RISER DIAGRAM SHOWS EACH 125 MCB | | | PANEL RUNING AN INDIVIDUAL GROUNDING CONDUCTOR TO THE | | | ELECTRODE THIS WILL PROVIDE A PARALLEL PATH FOR THE | | | GROUNDED CONDUCTOR. | | | PLEASE MAKE SURE ALL DISCONNECTS ARE SERVICE RATED A | | | NOTE WILL SUFFICE. NEC 250, 300 | | | | | | L |
|