2016-03-16 13:11:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
 ALTERNATE CONTACT
  
  
 NEC 230.23 A SERVICE CONDUCTORS SHALL HAVE SUFFICIENT
 AMPACITY TO CARRY CURRENT FOR THE LOAD AS CACULATED IN
 ACCORDANCE WITH ARTICLE 220.
 BOTH YOUR DEMAND LOADS ADD UP TOO 184 AMPS ( 92 + 92 )
 , THEREFORE A 150 AMP SERVICE IS NON-COMPLIANT MUST
 UPGRADE TO 200 OR RECALCULATE TO MATCH
 EXISTING RISER DIAGRAM. TABLE 310.16 B7 SHOWS 1/0 AWG
 IS GOOD FOR 175 AMPS NOT ENOUGH FOR LOAD CAPACITY.
  
 THE GROUNDING DETAIL RISER DIAGRAM SHOWS EACH 125 MCB
 PANEL RUNING AN INDIVIDUAL GROUNDING CONDUCTOR TO THE
 ELECTRODE THIS WILL PROVIDE A PARALLEL PATH FOR THE
 GROUNDED CONDUCTOR.
 PLEASE MAKE SURE ALL DISCONNECTS ARE SERVICE RATED A
 NOTE WILL SUFFICE. NEC 250, 300
  