| Plan Review Notes For Permit 15120386 |
| Permit Number |
15120386 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-04-26 09:49:34 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120386 | | | 4/26/16 | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE KITCHEN EXHAUST | | | HOODS IN THE SPACE, HOWEVER THE FOLLOWING COMMENTS | | | REGARDING THE HOODS WILL ALSO AFFECT HOW THE MAIN PLANS | | | HVAC SYSTEMS ARE DESIGNED. | | | | | | 1) THE REVISED PLAN SHOWS THE HOOD FOR THE CONVECTION | | | OVEN HAS BEEN REMOVED. REFER TO SECTION 507.2.2 AND | | | PROVIDE A TYPE II HOOD FOR THE OVEN OR VERIFY THAT THE | | | HEAT AND MOISTURE LOAD HAS BEEN INCORPORATED INTO THE | | | HVAC SYSTEM DESIGN, AND THE SPACE CONTAINING THE OVEN | | | WILL BE PROVIDED WITH EXHAUST AT A RATE OF .70 CFM PER | | | SF. PLEASE NOTE THAT THE AIR BALANCE CALCULATIONS MAY | | | HAVE TO BE REVISED. | | | 2) REFER TO SECTION 508.1 AND INDICATE HOW THE MAKEUP | | | AIR FOR HOOD A WILL BE AUTOMATICALLY CONTROLLED TO | | | START AND OPERATE SIMULTANEOUSLY WITH THE MAKEUP AIR | | | SYSTEM. PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.2 | | | FOR MAKEUP AIR TEMPERATURE WILL ALSO HAVE TO BE | | | VERIFED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|