2016-04-26 09:49:343RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120386
 4/26/16
  
 A SEPARATE PERMIT IS REQUIRED FOR THE KITCHEN EXHAUST
 HOODS IN THE SPACE, HOWEVER THE FOLLOWING COMMENTS
 REGARDING THE HOODS WILL ALSO AFFECT HOW THE MAIN PLANS
 HVAC SYSTEMS ARE DESIGNED.
  
 1) THE REVISED PLAN SHOWS THE HOOD FOR THE CONVECTION
 OVEN HAS BEEN REMOVED. REFER TO SECTION 507.2.2 AND
 PROVIDE A TYPE II HOOD FOR THE OVEN OR VERIFY THAT THE
 HEAT AND MOISTURE LOAD HAS BEEN INCORPORATED INTO THE
 HVAC SYSTEM DESIGN, AND THE SPACE CONTAINING THE OVEN
 WILL BE PROVIDED WITH EXHAUST AT A RATE OF .70 CFM PER
 SF. PLEASE NOTE THAT THE AIR BALANCE CALCULATIONS MAY
 HAVE TO BE REVISED.
 2) REFER TO SECTION 508.1 AND INDICATE HOW THE MAKEUP
 AIR FOR HOOD A WILL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE MAKEUP AIR
 SYSTEM. PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.2
 FOR MAKEUP AIR TEMPERATURE WILL ALSO HAVE TO BE
 VERIFED.
  