2016-03-28 14:14:502ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120386
 3/28/16
  
 1) SHEET M-1: THE O/A CALCULATIONS MUST INCLUDE THE
 REQUIRED 7.5 CFMS OF O/A PER PERSON AS REQUIRED BY
 TABLE 403,3.2
 2) M-1: EF-1, SHOWN AT THETYPE II HOOD LOCATION ON THE
 PLAN, IS NOTED TO BE 350 CFMS, BUT EF-1 IS LISTED AT 75
 CFMS IN THE SCHEDULE- PLEASE CLARIFY AND ALSO SHOW THE
 LOCATIONS OF EF-2 AND EF-3 ON THE PLANS. HOW MANY
 EXHAUST HOODS ARE IN THIS SPACE? PLEASE SHOW THE
 LOCATIONS OF THE HOODS ON THE PLANS AND INCLUDE THEM IN
 THE KITCHEN EQUIPMENT SCHEDULE.
 3) PLEASE SUBMIT MANUFACTURER'S CUT SHEETS AND
 MIAMI-DADE NOAS FOR THE ROOF FANS WITH REVIEW AND
 APPROVAL SIGNATURES BY THE E.O.R.
 4) PROVIDE A DUPLICATE SET OF ENERGY AND AC LOAD
 CALCULATIONS- ONLY ONE SET HAS BEEN SUBMITTED.
  