| Plan Review Notes For Permit 15120386 |
| Permit Number |
15120386 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-28 14:14:50 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15120386 | | | 3/28/16 | | | | | | 1) SHEET M-1: THE O/A CALCULATIONS MUST INCLUDE THE | | | REQUIRED 7.5 CFMS OF O/A PER PERSON AS REQUIRED BY | | | TABLE 403,3.2 | | | 2) M-1: EF-1, SHOWN AT THETYPE II HOOD LOCATION ON THE | | | PLAN, IS NOTED TO BE 350 CFMS, BUT EF-1 IS LISTED AT 75 | | | CFMS IN THE SCHEDULE- PLEASE CLARIFY AND ALSO SHOW THE | | | LOCATIONS OF EF-2 AND EF-3 ON THE PLANS. HOW MANY | | | EXHAUST HOODS ARE IN THIS SPACE? PLEASE SHOW THE | | | LOCATIONS OF THE HOODS ON THE PLANS AND INCLUDE THEM IN | | | THE KITCHEN EQUIPMENT SCHEDULE. | | | 3) PLEASE SUBMIT MANUFACTURER'S CUT SHEETS AND | | | MIAMI-DADE NOAS FOR THE ROOF FANS WITH REVIEW AND | | | APPROVAL SIGNATURES BY THE E.O.R. | | | 4) PROVIDE A DUPLICATE SET OF ENERGY AND AC LOAD | | | CALCULATIONS- ONLY ONE SET HAS BEEN SUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] |
|