| 2016-04-06 07:11:03 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120386 |
| | ADD: 2087 PALM BEACH LAKES BLVD./ DUNKIN DONUTS |
| | CONT: VENTURA ARCHITECTURE/ DEVELOPMENT INC. |
| | TEL: (954)423-1362 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: APRIL 06/2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. PLEASE NOTE THE SHELL BUILDING IS NOT |
| | COMPLETE. A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (LM DEVELOPMENT GROUP) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| | PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITHIN THE |
| | DOCUMENT. |
| | |
| | 2) COMPLIED.THE COVERSHEET CS-1 INDICATES THE TENANT |
| | BUILD OUT PLANS ARE DESIGNED TO THE 2010 FBC-B. JUNE |
| | 30/ 2015 THE FIFTH EDITION OF THE FLORIDA BUILDING CODE |
| | WAS ADOPTED STATEWIDE. PLEASE UPDATE THE PLANS TO THE |
| | CURRENT CODE. |
| | |
| | 3) SEMI-COMPLIED. ONCE THE ENERGY GAUGE TOTAL BUILDING |
| | PERFORMANCE AND INPUT DATA REPORT FORMS ARE CODE |
| | COMPLIANT, THEY WILL NEED TO BE SUBMITTED UNDER THE |
| | BASE SHELL PERMIT AS WELL FOR FIELD VARIFICATION OF |
| | MATERIALS USED AND INSTALLED MATCH THAT OF THE INPUT |
| | DATA REPORT. COOPERATION BETWEEN THE SHELL AND TENANT |
| | BUILD-OUT CONTRACTORS IS VITAL TO KEEP THIS PROJECT |
| | MOVING FORWARD. |
| | |
| | 4A) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL |
| | PERMIT. SHEET M-1 DETAIL # 2 FOR ROOF TOP A/C STAND |
| | PLEASE PROVIDE A PRODUCT APPROVAL. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) RROOFING PRODUCTS, ROOF CURBS AND ROOF TOP |
| | FANS, INTAKE AND EXHAUST. |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4B) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL |
| | PERMIT. SHEET M-1 DETAIL # 4 SHOWS A EXHAUST FAN AND |
| | CURB. A PRODUCT APPROVAL WILL ALSO BE REQUIRED FOR ALL |
| | ROOF TOP EXHAUST FANS. |
| | |
| | 4C) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL |
| | PERMIT. NOTE, TO DATE THE SHELL CONTRACTOR HAS |
| | REQUESTED ALL OF THE PRODUCT APPROVALS TO BE DEFERRED |
| | UNTIL AFTER PERMIT ISSUANCE. WE HAVE NOT SEEN ANY ROOF |
| | TOP CURBS FOR THE ROOF TOP A/C DOWN UNIT, NOR FASTENING |
| | OF THE CURB TO THE ROOF. 107.2.1.3 ADDITIONAL |
| | INFORMATION THAT MAY VERY FROM WHAT YOU HAVE DESIGN |
| | FOR. THE SHELL BUILDING PERMIT IS JUST THAT A SHELL |
| | BUILDING NO A/C EQUIPMENT. |
| | |
| | 4D) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL |
| | PERMIT. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5) 2ND REQUEST. PUTTING A NOTE ON THE PLANS TO COMPLY |
| | WITH THE CODE SECTION DOES NOT CONSTITUTE COMPLIANCE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART. |
| | |
| | SHEET A-1 PLEASE SHOW COMPLIANCE WITH THE 2014 FLORIDA |
| | ACCESSIBILITY : |
| | |
| | 5A)2ND REQUEST. 226.1 GENERAL. WHERE DINING SURFACES |
| | ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT |
| | LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING |
| | SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. IN |
| | ADDITION, WHERE WORK SURFACES ARE PROVIDED FOR USE BY |
| | OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY |
| | WITH 902. |
| | |
| | 5B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. |
| | |
| | 5C) 2ND REQUEST. 227 SALES AND SERVICE 227.1 GENERAL. |
| | WHERE PROVIDED, CHECK-OUT AISLES, SALES COUNTERS, |
| | SERVICE COUNTERS, FOOD SERVICE LINES, QUEUES, AND |
| | WAITING LINES SHALL COMPLY WITH 227 AND 904. |
| | |
| | 5D) 2ND REQUEST. 902.4.2 HEIGHT. THE TOPS OF TABLES AND |
| | COUNTERS SHALL BE 26 INCHES (660 MM) MINIMUM AND 30 |
| | INCHES (760 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |