| Plan Review Notes For Permit 15120386 |
| Permit Number |
15120386 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-16 16:16:28 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | 1.SHEET CS1 PLUMBING TO BE DESIGNED TO FBC PL 2014 5TH | | | ADDITION. | | | 2.SHEET A-5 DETAIL D WOMAN'S BATHROOM COAT HOOK SHALL | | | BE 48" MAX TO COMPLY WITH FBC ACC 603.4 | | | 3.GRAB BARS SHALL BE MEASURE TO TOP OF GRIPPING SURFACE | | | TO FF 33" MIN -36" MAX TO COMPLY WITH FBC ACC SEC 609.4 | | | 4. SHEET A-5 SHOW LAVS TO COMPLY WITH FBC ACC SEC606.2 | | | AND 306 | | | 5. SHEET P-1 GREASE RISER DIAGRAM IS MISSING P6 UNDER | | | ICE COFFEE MACHINE NEXT TO BAKERY CASE ALSO MISSING P18 | | | NEXT TO WALK IN FREEZER . IT SHOWS A P4 WHERE THE MOP | | | SINK IS IT SHOULD BE A P8. SHOW VENTS OFF WET VENT NOT | | | OFF FLOOR SINKS.PER FBC PL SEC 912 | | | 5. PROVIDE SANITARY RISER DIAGRAM. PER WPB AMEND. TO | | | FBC SEC 107.3.5.1.3(13) | | | 6.SHOW WC AND MOP SINK AND P15,P11 ON WATER RISER | | | DIAGRAM. PER WPB AMEND. TO FBC SEC 107.2.1 | | | 7. NOTE MANUFACTURE AND MODEL OF WATER FILTER TO COMPLY | | | WITH APPLICABLE STANDARDS. | | | 8. PROVIDE MODEL AND SIZING CALCULATION FROM | | | MANUFACTURE FOR GREASE TRAP. PER WPB AMEND. TO FBC SEC | | | 107.2.1 |
|