| 2015-12-18 10:23:46 | 1ST REVIEW 2014 MECHANICAL |
| | PERMIT 15120386 |
| | 12/18/15 |
| | |
| | 1) SHEET M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | RETURN AIR SYSTEMS OF RTU- 1 & 2 PER SECTION 606.2.1. |
| | INDICATE THE LOCATIONS OF THE REQUIRED DEVICES ON THE |
| | PLAN AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY |
| | THE DESIGN PROFESSIONAL. |
| | 2) AN EXHAUST RATE OF 0.7 CFM PER SQ.FT. IS REQUIIRED |
| | FOR THE KITCHEN PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A CALCULATION TO VERIFY COMPLIANCE. |
| | 3) THE AC CALCULATIONS PASTED ON THE M1 SHEET IS |
| | INCOMPLETE AND IS SPECIFYING THE WRONG LOCATION. PLEASE |
| | PROVIDE CALCULATIONS FOR THE WEST PALM BEACH SUBMITTED |
| | IN HARD COPY, AND INCLUDE HEAT LOAD FROM APPLIANCES. |
| | 4) PROVIDE SITE SPECIFIC WIND LOAD TIE DOWN |
| | ENGIONEERING FOR THE RTU'S IN COMPLIANCE WITHN SECTION |
| | 301.15 FBC-14 MECHANICAL. INCLUDE DESIGN CRITERIA AND |
| | SHOW DETAILS FOR ATTACHING THE CURB TO THE STRUCTURE, |
| | AND THE RTU TO THE CURB, PROVIDE A SUBMITTAL OR PRODUCT |
| | APPROVAL FOR THE CURB REVIEWED AND APPROVED BY THE |
| | DESIGN PROFESSIONAL. |
| | 5) PLACE A NOTE ON THE PLAN INDICATING SEPARATE PERMITS |
| | REQUIRED FOR THE HOOD, AND THE WALK-IN COOLER/FREEZER. |
| | 6) SHOW COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 |
| | ENERGY CONSERVATION- SHUTOFF DAMPER CONTROLS FOR O/A |
| | AIR. |
| | 7) PROVIDE AN MECHANICAL ROOF PLAN INDICATING LOCATIONS |
| | OF ALL EXHAUST OUTLETS AND AIR INLETS, AND CLEARANCE |
| | DISTANCE MEASUREMENTS- SEE SECTIONS 401.4, 501.3.1 |
| | FBC-10 MECHANICAL. PLEASE ALSO REVIEW SECTIONS 304.11 |
| | AND 306.5 FOR APPLICABILITY TO THE PROPOSED ROOFTOP |
| | EQUIPMENT. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |