Plan Review Notes
Plan Review Notes For Permit 15120386
Permit Number 15120386
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-18 10:23:461ST REVIEW 2014 MECHANICAL
 PERMIT 15120386
 12/18/15
  
 1) SHEET M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF RTU- 1 & 2 PER SECTION 606.2.1.
 INDICATE THE LOCATIONS OF THE REQUIRED DEVICES ON THE
 PLAN AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL.
 2) AN EXHAUST RATE OF 0.7 CFM PER SQ.FT. IS REQUIIRED
 FOR THE KITCHEN PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A CALCULATION TO VERIFY COMPLIANCE.
 3) THE AC CALCULATIONS PASTED ON THE M1 SHEET IS
 INCOMPLETE AND IS SPECIFYING THE WRONG LOCATION. PLEASE
 PROVIDE CALCULATIONS FOR THE WEST PALM BEACH SUBMITTED
 IN HARD COPY, AND INCLUDE HEAT LOAD FROM APPLIANCES.
 4) PROVIDE SITE SPECIFIC WIND LOAD TIE DOWN
 ENGIONEERING FOR THE RTU'S IN COMPLIANCE WITHN SECTION
 301.15 FBC-14 MECHANICAL. INCLUDE DESIGN CRITERIA AND
 SHOW DETAILS FOR ATTACHING THE CURB TO THE STRUCTURE,
 AND THE RTU TO THE CURB, PROVIDE A SUBMITTAL OR PRODUCT
 APPROVAL FOR THE CURB REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL.
 5) PLACE A NOTE ON THE PLAN INDICATING SEPARATE PERMITS
 REQUIRED FOR THE HOOD, AND THE WALK-IN COOLER/FREEZER.
 6) SHOW COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION- SHUTOFF DAMPER CONTROLS FOR O/A
 AIR.
 7) PROVIDE AN MECHANICAL ROOF PLAN INDICATING LOCATIONS
 OF ALL EXHAUST OUTLETS AND AIR INLETS, AND CLEARANCE
 DISTANCE MEASUREMENTS- SEE SECTIONS 401.4, 501.3.1
 FBC-10 MECHANICAL. PLEASE ALSO REVIEW SECTIONS 304.11
 AND 306.5 FOR APPLICABILITY TO THE PROPOSED ROOFTOP
 EQUIPMENT.
  