2015-12-16 13:30:39PERMIT # 15120386
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SHEET A-2 HAS A NOTE THAT READS "MENU BOARD SIZE AND
 LOCATION TO BE DETERMINED ON A SITE BY SITE BASIS." IT
 HAS BEEN OBSERVED AT OTHER DD LOCATIONS THAT THE MENU
 BOARD IS INSTALLED DIRECTLY ABOVE THE OVEN(S) AND/OR
 DIRECTLY UNDER THE HOOD SYSTEM. THIS PRACTICE IS NOT
 RECOMMENDED DUE TO THE DIRECT EXPOSURE TO HEAT AND
 SHOULD BE AVOIDED.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM. (NFPA 72 IS REFERENCED
 UNDER APPLICABLE CODES.)
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  