2016-01-06 15:46:591ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011 FBC 2014
 2- RECEPTACLES WITHIN 6' OF SINK REQUIRE GFCI 210.8.A7
 3- COMMERCIAL KITCHENS GFCI 15 / 20 AMP OUTLETS NEC
 210.8B2
 4- FBC E C-405 LIGHTING CONTROLS IN INTERIOR /
 BATHROOMS AND RECCESSED
 LIGHTS MUST BE IC RATED AND SEALED.
 5- FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 6- PLEASE PROVIDE AIC CALCS OF OCPD AND SHORT CIRCUIT
 RATING OF EQUIPMENT NEC 110.10 / 110.9
 7- FIRE ALARM ON A SEPERATE PERMIT. IMPORTANT NOTICE
 ALL AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION
  