| Plan Review Notes For Permit 15120386 |
| Permit Number |
15120386 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-06 15:46:59 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011 FBC 2014 | | | 2- RECEPTACLES WITHIN 6' OF SINK REQUIRE GFCI 210.8.A7 | | | 3- COMMERCIAL KITCHENS GFCI 15 / 20 AMP OUTLETS NEC | | | 210.8B2 | | | 4- FBC E C-405 LIGHTING CONTROLS IN INTERIOR / | | | BATHROOMS AND RECCESSED | | | LIGHTS MUST BE IC RATED AND SEALED. | | | 5- FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | 6- PLEASE PROVIDE AIC CALCS OF OCPD AND SHORT CIRCUIT | | | RATING OF EQUIPMENT NEC 110.10 / 110.9 | | | 7- FIRE ALARM ON A SEPERATE PERMIT. IMPORTANT NOTICE | | | ALL AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY | | | MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF | | | AN ALARM CONDITION | | | |
|