| 2015-12-15 15:30:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120386 |
| | ADD: 2087 PALM BEACH LAKES BLVD./ DUNKIN DONUTS |
| | CONT: VENTURA ARCHITECTURE/ DEVELOPMENT INC. |
| | TEL: (954)423-1362 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE SHELL BUILDING IS NOT COMPLETE. A |
| | LETTER FROM THE QUALIFIER OF BOTH THE SHELL CONTRACTOR |
| | (LM DEVELOPMENT GROUP) AND TENANT BUILD-OUT CONTRACTOR |
| | MUST BE PROVIDED BEFORE TENANT BUILD-OUT PERMIT CAN BE |
| | ISSUED, IF THE TENANT BUILD-OUT CONTRACTOR WISHES TO |
| | START WORK BEFORE THE SHELL WORK HAS RECEIVED A |
| | CERTIFICATE OF COMPLETION, AGREEING THEY WILL WORK |
| | TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE DOCUMENTS |
| | WILL NEED TO BE SIGNED BY THE QUALIFIER. PLEASE PROVIDE |
| | THE PERMIT NUMBER, ADDRESS WITHIN THE DOCUMENT. |
| | |
| | 2) THE COVERSHEET CS-1 INDICATES THE TENANT BUILD OUT |
| | PLANS ARE DESIGNED TO THE 2010 FBC-B. JUNE 30/ 2015 THE |
| | FIFTH EDITION OF THE FLORIDA BUILDING CODE WAS ADOPTED |
| | STATEWIDE. PLEASE UPDATE THE PLANS TO THE CURRENT CODE. |
| | |
| | 3) PLEASE NOTE THERE ARE DESIGN CONCEPTS WITHIN THE |
| | TENANT BUILD OUT PLANS THAT VARIES FROM THE SHELL |
| | PERMIT. ON THE M-1 SHEET DETAILS 2 & 4 BOTH INDICATE A |
| | CONCRETE TYPE ROOF DECK. THE SHELL PERMITED SET OF |
| | PLANS SHOWS A BAR JOIST SYSTEM, 1 1/2 INCH 22 GAGE G90 |
| | "B" TYPE DECK ON SHEET S-2. ON THE A5 SHEET |
| | THE PLANS CALL OUT IN DETAILS 6 & 7 FOR R-19 RIGID |
| | INSULATION AND A TPO 60 MIL ROOFING SYSTEM. IN THE |
| | TENANT BUILD-OUT ENERGY INPUT DATA REPORT THE ROOF |
| | INDICATES A R-30 VALUE FOR THE INSULATION BOARD. THESE |
| | DISCREPANCIES WILL NEED TO BE WORKED OUT BETWEEN THE |
| | TWO DESIGN TEAMS BEFORE PERMIT ISSUANCE CAN OCCUR ON |
| | THE TENANT BUILD OUT. DISCREPANCY IN PLANS. 107.2.1.3. |
| | |
| | 4A) SHEET M-1 DETAIL # 2 FOR ROOF TOP A/C STAND PLEASE |
| | PROVIDE A PRODUCT APPROVAL. FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) RROOFING PRODUCTS, ROOF CURBS AND ROOF TOP |
| | FANS, INTAKE AND EXHAUST. |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4B) SHEET M-1 DETAIL # 4 SHOWS A EXHAUST FAN AND CURB. |
| | A PRODUCT APPROVAL WILL ALSO BE REQUIRED FOR ALL ROOF |
| | TOP EXHAUST FANS. |
| | |
| | 4C) NOTE, TO DATE THE SHELL CONTRACTOR HAS REQUESTED |
| | ALL OF THE PRODUCT APPROVALS TO BE DEFERRED UNTIL AFTER |
| | PERMIT ISSUANCE. WE HAVE NOT SEEN ANY ROOF TOP CURBS |
| | FOR THE ROOF TOP A/C DOWN UNIT, NOR FASTENING OF THE |
| | CURB TO THE ROOF. 107.2.1.3 ADDITIONAL INFORMATION THAT |
| | MAY VERY FROM WHAT YOU HAVE DESIGN FOR. THE SHELL |
| | BUILDING PERMIT IS JUST THAT A SHELL BUILDING NO A/C |
| | EQUIPMENT. |
| | |
| | 4D) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5) SHEET A-1 PLEASE SHOW COMPLIANCE WITH THE 2014 |
| | FLORIDA ACCESSIBILITY : |
| | |
| | 5A) 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED |
| | FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 |
| | PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION, |
| | WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN |
| | EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902. |
| | |
| | 5B) 226.2 DISPERSION. |
| | DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY |
| | WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR |
| | FACILITY CONTAINING DINING SURFACES AND WORK SURFACES. |
| | |
| | 5C) 227 SALES AND SERVICE 227.1 GENERAL. WHERE |
| | PROVIDED, CHECK-OUT AISLES, SALES COUNTERS, SERVICE |
| | COUNTERS, FOOD SERVICE LINES, QUEUES, AND WAITING LINES |
| | SHALL COMPLY WITH 227 AND 904. |
| | |
| | 5D) 902.4.2 HEIGHT. THE TOPS OF TABLES AND COUNTERS |
| | SHALL BE 26 INCHES (660 MM) MINIMUM AND 30 INCHES (760 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | |
| | |
| | |
| | |
| | |