| Plan Review Notes For Permit 15120385 |
| Permit Number |
15120385 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-15 13:19:23 | 1) PLEASE SUBMIT A NARRATIVE FROM THE DESIGN | | | PROFESSIONAL THAT CLEARLY DESCRIBES THE CHANGES THAT | | | WERE MADE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SUBMIT A COMPRESSED AIR RISER SHOWING THE TYPE OF | | | PIPE MATERIAL, PIPE SIZES, VALVE LOCATION, SUPPORTS, | | | ETC. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHOW THE LOCATION OF THE AIR COMPRESSORS. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 4) WHERE ARE THE RELOCATED VACUUM UNITS THAT WERE IN | | | THE CENTRAL VACUUM BUILDING? | | | 5) SHT. P-2 - PART OF THE SANITARY AND WATER RISER IS | | | CUT OFF ON DETAIL #6 ON P-2. | | | 6) SHT. P-4 SHOWS 4 OIL SEPARATORS ON THE RISER AND | | | ONLY 3 ON P-1. CLARIFY. | | | 7) THE SANITARY RISER ON P-4 FOR THE UNDERGROUND | | | EXTERIOR SANITARY LINE DOES NOT MATCH THE PLAN VIEW ON | | | SHT.P-1. CLARIFY, | | | 8) SHT. P-4 - PLEASE IDENTIFY THE OIL SEPARATORS AS | | | SUCH. THEY ARE LABELED AS GREASE TRAPS. | | | 9) A LINT INTERCEPTOR WITH A WIRE BASKET SHALL BE | | | INSTALLED ON THE WASHING MACHINE DRAIN PER FBC-PLUMBING | | | SEC.1003.6. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|