| 2015-12-15 14:50:57 | THIS PERMIT IS BEING CONDITIONALLY APPROVED AS NOTED: | | | 1. RECORDS INDICATE THAT THIS WORK WAS BEGUN WITHOUT | | | THE BENEFIT OF A PERMIT. | | | 2. THE INTER-SYSTEM BONDING TERMINAL SHALL BE INSTALLED | | | AS REQUIRED BY NEC 250.94. | | | 3. THE SUPPLEMENTAL GROUNDING ELECTRODE SHALL BE | | | INSTALLED AS REQUIRED IN NEC 250.53 | | | 4. SMOKE DETECTORS SHALL BE INSTALLED AS REQUIRED IN | | | FBC-R 314. | | | 5. PROVIDED LOAD CALCS DO NOT APPEAR CORRECT AND WILL | | | BE VERIFIED BE FIELD INSPECTOR. | | | | | | ALL WORK SUBJECT TO FIELD INSPECTOR'S APPROVAL. |
|