| 2016-02-17 09:45:14 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15120344 |
| | 2/17/16 |
| | |
| | 1) AN ENGINEERING PACKAGE FOR INSTALLATION OF TRANE |
| | RTU'S HAS BEEN SUBMITTED WITH AN OUTDATED COPIED |
| | SIGNATURE AND SEAL FROM DOUGLAS RUGGIANO P.E. PLEASE |
| | NOTE THAT ALL ENGINEERING SUBMITTALS SHALL BE CURRENTLY |
| | DATED, AND BEAR THE ORIGINAL SIGNATURE AND SEAL OF THE |
| | ENGINEER OF RECORD- SECTION 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE. PLEASE CLARIFY WHICH STRUCTURAL |
| | ENGINEER IS THE EOR FOR TIE DOWN OF THE TRANE RTU'S- |
| | MR. RUGGIANO OR G.D. KLIEGER WHOSE SIGNATURE AND SEAL |
| | APPEARS ON THE REVISED STRUCTURAL DRAWINGS. THE |
| | MECHANICAL ENGINEERS- CREDO APPEAR TO BE ON BOARD WITH |
| | MR. RUGGIANO BY VIRTUE OF THEIR SHOP DRAWING APPROVAL |
| | STAMPS ON THE TRANE DOCS. |
| | 2) A PERMIT APPLICATION AND SPECIFICATIONS FOR THE |
| | GLYCOL BEER CHILLER SYSTEMS HAS BEEN ATTACHED NOW TO |
| | THIS PERMIT, HOWEVER THERE IS NO VALUE SHOWN ON THE |
| | APPLICATION. PLEASE NOTE THE APPROVED PLANS FOR THE |
| | TWIN PEAKS RESTAURANT (PERMIT #15060045) SHOWS THE |
| | GLYCOL SYSTEM TO BE INSTALLED "BY OTHERS"- SEE SHEETS |
| | FS-2.1 AND M2.1. THE FOUR ROOF TOP CONDENSERS AND BEER |
| | RUN LINES ARE SHOWN FOR REFERENCE ONLY. IN ACCORDANCE |
| | WITH SECTION 109.3 WPB AMENDMENTS TO THE FBC-10 |
| | BUILDING CODE, A TOTAL VALUE THAT INCLUDES LABOR, |
| | MATERIALS, AND EQUIPMENT SHALL BE PLACED ON THE |
| | APPLICATION. IF THE CONTRACTOR DOES NOT PROVIDE AN |
| | ACCURATE COST FOR THE PROJECT, THAN A VALUE WILL BE |
| | PLACED ON THE APPLICATION BASED ON CURRENT NATIONAL |
| | VALUATION TABLES, AND APPROPRIATE PERMITTING FEES WILL |
| | BE CHARGED. |
| | 3) PROVIDE SITE SPECIFIC WIND LOAD TIE-DOWN ENGINEERING |
| | FOR THE FOUR GLYCOL SYSTEM CONDENSERS AND ROOF STANDS- |
| | SECTION 301.12 FBC-10 MECHANICAL. |
| | |
| | CHRISTOPHER L. COLE |