| Plan Review Notes For Permit 15120344 |
| Permit Number |
15120344 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-11 07:30:09 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT SUBMITTAL #15120344 | | | MASTER #15060045 | | | 12/11/15 | | | | | | 1) THE RTU SUBMITTAL IS FOR TRANE MODEL UNITS, HOWEVER | | | LENNOX MODELS ARE SHOWN ON THE MAIN BUILDING PLANS. | | | PROVIDE A SUBMITTAL FOR THE LENNOX MODELS, OR REVISE | | | THE MAIN PLAN TO INDICATE TRANE MODELS. | | | 2) THE AAON SUBMITTAL INCLUDES FL. PRODUCT APPROVAL # | | | WITH MULTIPLE CURB MODELS THAT HAVE TO BE MATCHED WITH | | | THE UNIT MODEL SELECTED FOR INSTALLATION. THE EOR MUST | | | MARKUP THE DOCUMENT INDICATING WHICH CURB (STANDARD OR | | | HEAVY DUTY), AND WHICH ATTACHMENT CLIP HE IS SELECTING | | | FOR INSTALLATION- SEE PAGE 5. PLEASE NOTE THAT THE RTU | | | INSTALLATION DETAILS BY KLIEGER P.E THAT ARE SHOWN ON | | | THE MAIN PLAN SHEET S-2 SHOW A DIFFERENT METHOD OF | | | INSTALLATION, AND ARE NOT SPECIFIC TO THE SELECTED | | | ROOFTOP UNITS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|