2015-12-14 16:44:05 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120344
 MASTER: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: MACHIN MECHANICAL
 TEL: 954-702-3390
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: MON. DEC. 21/2015
 ACTION: DENIED
  
 1) THE MASTER PERMIT ON SHEETS 39/72 M0.1 AND SHEET S-2
 SHEET 59/72 BOTH SHOW GENERIC CONNECTIONS OF THE ROOF
 TOP CURB UNITS. SUBMITTAL # 10 PAGE 17OF 36 SHOWS A
 ROOF TOP CURB TRANE U. S. DIMENSIONAL PLAN. NOTE THIS
 IS NOT A PRODUCT APPROVAL. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 CURBS, ROOF TOP INTAKE AND EXHAUST FANS, AND PRODUCTS
 INTRODUCED AS A RESULT OF NEW TECHNOLOGY.
  
 2) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) DISCREPANCY IN PLANS. THE SHEET 40 OF 72 SHEET M0.2
 SHOWS THE ROOF TOP PACKAGED UNITS AS LENNOX MODELS
 WHERE AS THE PAPERWORK BEING SUBMITTED UNDER THIS
 REVIEW ARE TRANE ROOF TOP CURBS AND ROOF TOP PACKAGE
 UNITS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, IT
 APPEARS A REVISION MAY BE REQUIRED?
  
 4) SUBMITTAL/ TRANSMITTAL # 11 IS FOR AAON ROOFTOP
 CURBS, THE COVERSHEET FOR THESE REPORTS WAS NOT
 INCLUDED IN THIS SUBMITTAL INDICATING THE REPORT IS A
 FLORIDA REPORT OR A MIAMI-DADE NOA? NEED TO IDENTIFY
 THE TESTING AGENCY AND PRODUCT APPROVAL NUMBER. THERE
 ARE VARIOUS REPORTS 10-AOI-0001, 15-2535 WHICH
 REPRESENT VARIOUS UNITS, PLEASE IDENTIFY THE REPORT TO
 THE UNIT. THE SECOND ISSUE WITHIN BOTH REPORTS
 TECHNICAL SHEET # 1 IDENTIFY THE CURB TYPE TYPE TIER
 1-4.
 TECHNICAL SHEET 5 IDENTIFY STEEL CLIP SCHEDULE STANDARD
 CURB VERSES HEAVY DUTY CURB. DETAIL 3 OF SHEET # 5 NOTE
 CLIP TYPE 1 & 2 MAY BE USED INTERCHANGEABLY WITH THIS
 DESIGN, SELECTION OF THE CLIP SHALL BE BY OTHERS, AGAIN
 IDENTIFY CLIP.
  
 5) EXHAUST FAN #6 SUBMITTAL/ TRANSMITTAL # 12 NOA-
 15-0729.19 TECHNICAL SHEET 1/3 PLEASE IDENTIFY THE
 MODEL AND CURB DIMENSIONS. PAGE 3 OF 3 PLEASE IDENTIFY
 MODEL, DECK TYPE AND AMOUNT OF FASTENERS FOR ANCHORING
 THE FANS CURB TO ROOF. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 6) FOR ALL 3 SUBMITTALS/ TRANSMITTALS THE MECHANICAL
 ENGINEER AFFIXED THEIR SHOP DRAWING STAMP OF APPROVALS,
 THE STRUCTURAL ENGINEER OF RECORD GERSHON KLIEGER SHOUD
 BE THE ENGINEER OF RECORD REVIEWING THESE SUBMITTALS
 SINCE THEY ARE COMPONENTS AND CLADDING AND DEAL WITH
 WIND.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  