| Plan Review Notes For Permit 15120326 |
| Permit Number |
15120326 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-01 19:54:19 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PASS WITH A PROVISO. | | | | | | - 4TH AND 17 TH FLOOR EXTERIOR SIGNAGE NEEDS TO BE ON A | | | COMBINATION OF A PHOTO SENSOR AND A TIME SWITCH OR AN | | | ASTRONAMICAL TIMER . FBC- E C405.2.4 EXTERIOR LIGHTING | | | CONTROLS. | | | - AVAILABLE FAULT CURRENT LABEL IS REQUIRED NEC 110.24 | | | A & B | | | |
|