| Plan Review Notes For Permit 15120325 |
| Permit Number |
15120325 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-17 12:10:24 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120325 | | | 12/17/15 | | | | | | 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR | | | THE NEW HEAT PUMPS IN LEVEL 6 - SEE SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014 | | | TO INCLUDE THE THE CHILLED WATER SYSTEM PIPING. PLEASE | | | SEE TABLE C403.2.3(10) FBC-14 ENERGY CONSERVATION. | | | 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN | | | ON THE HVAC PLANS ON LEVEL 6. | | | 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON | | | THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE | | | HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE | | | PROVIDED? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|