Plan Review Notes
Plan Review Notes For Permit 15120325
Permit Number 15120325
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-17 12:10:241ST REVIEW 2014 MECHANICAL
 PERMIT #15120325
 12/17/15
  
 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR
 THE NEW HEAT PUMPS IN LEVEL 6 - SEE SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014
 TO INCLUDE THE THE CHILLED WATER SYSTEM PIPING. PLEASE
 SEE TABLE C403.2.3(10) FBC-14 ENERGY CONSERVATION.
 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN
 ON THE HVAC PLANS ON LEVEL 6.
 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON
 THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE
 HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE
 PROVIDED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  