2015-12-29 17:45:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET A000, PROJECT INFORMATION STATES THAT THE
 CONSTRUCTION TYPE IS IIB, BUT OUR RECORDS SHOW THAT
 THIS BUILDING IS A TYPE I (PERMIT APPLICATION DATE
 1/27/87). PLEASE CLARIFY OR REVISE, FBC 107.
  
 2. SEE FBC 5TH ED. ACCESSIBILITY 404.2.6, TWO DOORS IN
 A SERIES, AND REVISE PLAN TO SHOW DISTANCE FROM THE
 ELEVATOR LOBBY PAIR OF DOORS TO THE LOBBY PAIR OF
 DOORS.
  
 3. SHEETS A003 AND A003A, ASSEMBLY OCCUPANT LOAD IS
 CORRECT IN "EGRESS REQUIREMENTS" AT 15SF/PERSON, BUT
 THE OCCUPANCY CLASSIF. LEGEND STATES THAT THE ACCESSORY
 ASSEMBLY AREA IS 100 SF/PERSON, PLEASE CORRECT.
  
 4. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, DESIGN FEES. PROVIDE A COPY OF THE
 CONTRACT FOR THIS PROJECT.
  
 5. FBC 5TH ED. ACCESSIBILITY 202.4, CONFIRM THAT
 EXISTING DRINKING FOUNTAINS AND RESTROOMS MEET THE
 REQUIREMENTS FOR ACCESSIBLITY.
  
  
  
  
  