Plan Review Notes
Plan Review Notes For Permit 15120324
Permit Number 15120324
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-14 11:08:571ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET. A 125-VOLT, SINGLE-PHASE, 15- OR 20-
 AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT AN
 ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED
 ON THE SAME LEVEL AND WITHIN 7.5 M (25 FT) OF THE
 HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE
 OUTLET SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT
 DISCONNECTING MEANS.
  
 -SHOW DISCONNECTING MEANS FOR AHU 1 AND 2 AND ALSO
 SERVICING OUTLET.
  
 - SEPERATE PERMIT FOR GENERATOR
  
  