| Plan Review Notes For Permit 15120324 |
| Permit Number |
15120324 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-14 11:08:57 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION | | | EQUIPMENT OUTLET. A 125-VOLT, SINGLE-PHASE, 15- OR 20- | | | AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT AN | | | ACCESSIBLE | | | LOCATION FOR THE SERVICING OF HEATING, | | | AIR-CONDITIONING, | | | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED | | | ON THE SAME LEVEL AND WITHIN 7.5 M (25 FT) OF THE | | | HEATING, | | | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE | | | RECEPTACLE | | | OUTLET SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE | | | EQUIPMENT | | | DISCONNECTING MEANS. | | | | | | -SHOW DISCONNECTING MEANS FOR AHU 1 AND 2 AND ALSO | | | SERVICING OUTLET. | | | | | | - SEPERATE PERMIT FOR GENERATOR | | | | | | |
|