2015-12-23 07:42:001ST REVIEW 2010 MECHANICAL
 REVISION PERMIT #15120322
 12/23/15
  
 1) THE REVISED AC LAYOUT PLAN SHOWS THE AMOUNT OF CFM'S
 DISTRIBUTED WILL EXCEED THE CAPACAITIES OF THE TWO-
 5TON SYSTEMS. AC-1- 2515 CFMS, AC-2- 2690 CFMS. PER
 TELEPHONE CONVERSATION WITH DAVID R. JONES P.E. ON
 12/22/15, THE LAYOUT IS INCORRECT AND WILL BE REVISED.
  