| Plan Review Notes For Permit 15120320 |
| Permit Number |
15120320 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-15 12:30:58 | MECHANICAL PROVISIOS: | | | 3/15/16 | | | | | | 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE AC SYSTEMS SHALL BE ON-SITE AT | | | TIME OF INSPECTION. | | | 2) THE AC CONDENSERS SHALL BE INSTALLED AT OR ABOVE THE | | | REQUIRED FLOOD ELEVATION HEIGHT PER SECTION R322.1.6 | | | FBC-14 RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|